IO Setup
To invert the function, switch to
“
ON
”
(display
|
- - - -
|
as long as no function is allocated
for D2).
OFF
D2 Inverting
IO Setup
With networking the digital inputs can be replaced by control over bus (Slave interface
2A/2B).
With mode of operation
4.03
pre-setting of
“
D2
”
is
|
ON
|
.
If bus mode is at
|
ON
|
, the digital input can be set by coil register c1 for D2.
ON
D2 Busmode
IO Setup
If the digital inputs have the
same
function allocation (also applies for timer function)
you can choose between an AND and OR operation.
OR
operation (factory setting). The function becomes active
when one
of the digital
inputs or the timer is activated.
AND
operation. The function becomes active
when all
digital inputs or also the timer
are activated.
OG
D - D Relation
Function
Description
OFF
No function (factory setting)
Enable
(1D)
Enable (remote control)
“
ON
”
/
“
OFF
”
External error
(2D)
External fault alarm
Limit
(3D)
“
Limit
”
ON / OFF
In
fl
uences control circuit 1 and control circuit 2 in operation with two control circuits
E1 / E2
(4D)
Switch over input
“
E1
”
/
“
E2
”
(for operation with one control circuit)
Reset
(10D)
Complete re-start of the device
Max. Speed
(11D)
Setting Max. Speed
“
ON
”
/
“
OFF
”
In
fl
uences the respectively set value
“
1. Max. Speed
”
and
“
2. Max. Speed
”
in operation
with two control circuits.
Motorheating
(12D)
Motorheating ON / OFF
Switch over direction
of rotation
(13D)
Reverse direction of rotation
“
right-hand
”
/
“
left-hand
”
(only for frequency inverter with
3 ~ output)
Freeze function
(14D)
“
Freeze function
”
= maintain momentary modulation value
Override Time
(21D)
Overwrite timer function (in operation with timer add-on module)
The timer output is overwritten for a settable time with a selectable status (ON / OFF).
For Mode Speed controller
1.01
1. Setpoint 1/2
(5D)
Switch over
“
Set Intern1
”
/
“
Set Intern2
”
“
Setting External 1
”
must be at
“
OFF
”
.
Setpoint int./ext.
(6D)
Switch over
“
Intern
”
/
“
Extern
”
For modes as controller (from
2.01.
)
1. Setpoint 1/2
(5D)
Switch over
“
Setpoint 1
”
/
“
Setpoint 2
”
for control circuit1
Setpoint Intern/Exter-
nal
(6D)
Switch over
“
Intern
”
/
“
Extern
”
Possible only for operation with one control circuit!
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003