![ZIEHL-ABEGG FXDM25 Скачать руководство пользователя страница 60](http://html1.mh-extra.com/html/ziehl-abegg/fxdm25/fxdm25_operating-instructions-manual_3796534060.webp)
Controller Setup
I-component = accuracy, correction time
Setting range: 0 - 200 %
bigger = faster
smaller = more slowly
50 %
KI
Controller Setup
D-component
More
“
D-component
”
causes more stability by a clean actual value signal with shorter
correction times
By a actual value signal with a superposition should be done to attitude without
“
D-
component
”
→
0 %
Setting range: 0 - 200 %
value smaller = less
“
D-component
”
value higher = more
“
D-component
”
50 %
KD
Controller Setup
Integration time = correction time
Setting range: 0 - 200 %
smaller = faster
bigger = more slowly
0 %
TI
9.9.9
Group control
9.9.9.1
Group version
Groups can be controlled by the analogue output
“
A
”
or the relay outputs
“
K1
”
and
“
K2
”
.
Controller Setup
Following group versions are available:
0
: One controlled group and up to three switched groups (factory setting)
1
: Two controlled groups
0
Group version
Information
•
The groups must be connected at the appropriate programmed output when activating by the
analogue outputs and relays.
•
The assignment of the analogue outputs and the relays for the group control takes place in the IO
Setup.
•
The number of possible groups depends on the available hardware outputs.
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
60/123