9.9.9.2
Group variant 0: One controlled group and up to three switched groups
Control group 2/3/4 via relais
Controller Setup
Group 2 ON value
Switch-on value for Group2
Setting range: 0 - 100 %
Factory setting: 50 % *
50 %
Group 2 ON value
Controller Setup
OFF Value Group2
Switch-off value for group2
Setting range: 0 - 100 %
Factory setting: 45 % *
45 %
OFF Value Group2
Controller Setup
nmin at Group2
Minimum Value for Group2
Setting range: 0 - 100 %
Factory setting: 20 % *
20 %
nmin at Group2
Controller Setup
Group 3 ON value
Switch-on value for Group3
Setting range: 0 - 100 %
Factory setting: 70 % *
70 %
Group 3 ON value
Controller Setup
OFF Value Group3
Switch-off value for group3
Setting range: 0 - 100 %
Factory setting: 65 *
65 %
OFF Value Group3
Controller Setup
nmin at Group3
Minimum Value for Group3
Setting range: 0 - 100 %
Factory setting: 30 % *
30 %
nmin at Group
3
Controller Setup
Group 4 ON value
Switch-on value for Group4
Setting range: 0 - 100 %
Factory setting: 85 % *
85 %
Group 4 ON value
Controller Setup
OFF Value Group4
Switch-off value for group4
Setting range: 0 - 100 %
Factory setting: 80 % *
80 %
OFF Value Group4
Controller Setup
nmin at Group4
Minimum Value for Group4
Setting range: 0 - 100 %
Factory setting: 40 % *
40 %
nmin at Group4
*
As long as in IO Setup
“
K Function
”
not programmed display:
|
- - - -
|
Higher settings must be selected for following groups and the switch-off value of the group must be
below the switch-on value.