![ZIEHL-ABEGG FXDM25 Скачать руководство пользователя страница 40](http://html1.mh-extra.com/html/ziehl-abegg/fxdm25/fxdm25_operating-instructions-manual_3796534040.webp)
9.2.6
For mode
2.03
Relay output for temperature monitoring
If the set value for the
“
minimum alarm
”
is not reached or the set value for the
“
maximum alarm
”
is
exceeded, a message is generated via the alarm symbol in the display. In addition,
„
Lmt E1 min
“
is
displayed alternately with the actual value for the minimum alarm and Lmt E1 max for the
„
Maximum
alarm
“
. An external message follows via the factory-assigned
“
K1
”
relay. (IO Setup: K1 function =
|
2K
|
).
Setting
Alarm Minimum
Setting range: OFF / -49.9...150.0
°
C
Factory setting: 0.0
°
C
0.0
°
C
Alarm Minimum
Setting
Alarm Maximum
Setting range: OFF / -49.9...150.0
°
C
Factory setting: 40.0
°
C
40.0
°
C
Alarm Maximum
Info
Example for display if falling below setting
“
Alarm Minimum
”
alternating to the actual
value display.
Relay
“
K1
”
disengages (if not inverted).
Lmt E1 min
Info
Example for display if exceeding setting
“
Alarm Maximum
”
alternating to the actual
value display
Relay
“
K1
”
disengages (if not inverted).
Lmt E1 max.
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
40/123