9.10.2.5
Switch over Input signal
“
E1
”
/
“
E2
”
, Function
|
4D
|
Switch over between Input signal 1 (Analog In 1 terminal
“
E1
”
) and input signal 2 (Analog In 2 terminal
“
E2
”
).
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
24V
D1 D1
1
0
n = 0- 100 %
0
1
Si 1
Si 2
E1
GND
E2
GND
Si 1
Si 2
26.05.2010
v_4d_umschaltung_e1_e2.vsd
Controller
Si 1
Signal 1
Si 2
Signal 2
For mode speed controller (
1.01
) Base setup for
“
E2 Analog In
”
:
|
1E
|
necessary.
For modes controller (higher
2.01
..) Base setup for
“
E2 Analog In
”
:
|
7E
|
necessary (as far as
otherwise does not occupy).
9.10.2.6
Set 1/2 or Setpoint 1/2, Function
|
5D
|
For Mode Speed controller
1.01
: Switch over
“
Set Intern1
”
/
“
Set Intern2
”
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
Controller
24V
D1 D1
1
0
n = 40 %
1
n = 80 %
0
- - - - -
- - - - -
11.05.2007
v_5d_vorgabe_intern_1_2.vsd
2
1
1
Setting
“
Set Intern1
”
(depending on device type in: %, Hz, rpm)
2
Setting
“
Set Intern2
”
(depending on device type in: %, Hz, rpm)
•
“
D1 Inverting
”
=
“
OFF
”
:
“
Set Intern1
”
at
opened contact /
“
Set Intern2
”
at closed
contact.
•
“
D1 Inverting
”
=
“
ON
”
:
“
Set Intern1
”
at
closed contact /
“
Set Intern2
”
at opened
contact.
Info
Operation with
“
Set Intern2
”
is signalized by the moon symbol for reduced operation.
“
Set extern1
”
under
“
settings
”
must be programmed to
“
OFF
”
.
50 %
Modulation
For operation as controller (starting from
2.01
): switch over
“
Setpoint 1
”
/
“
Setpoint 2
”
For operation with second control circuit: switch over
“
1.Setpoint 1
”
/
“
1.Setpoint 2
”
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
71/123