The time and date must be set during start-up operation and when using the real-time clock. The
device calculates the weekday based on the date.
In principle, the timer function acts like a digital switch input (timer
“
On
”
closed contact at inverting
OFF). The same functions can be assigned to the timer switch as the digital inputs(
“
D1 ..D2)
”
.
Information
The clock module type Z-Module-RTC and the add-on module type Z-MODULE-B both need the slot
|
X13
|
. That means that only one of the two modules can be used!
Function
Description *
Timer ON =
(@ Timer Invert. = OFF)
OFF
No function (factory setting)
Enable
(1D)
Enable (remote control)
“
ON
”
/
“
OFF
”
Device ON
External error
(2D)
External fault alarm
Failure
Limit
(3D)
“
Limit
”
ON / OFF
In
fl
uences control circuit 1 and control circuit 2 in operation
with two control circuits
Limit ON
E1 / E2
(4D)
Switch over input
“
E1
”
/
“
E2
”
(for operation with one control
circuit)
Signal at E2
Reset
(10D)
Complete re-start of the device
Reset
Max. Speed
(11D)
Setting Max. Speed
“
ON
”
/
“
OFF
”
In
fl
uences the respectively set value
“
1. Max. Speed
”
and
“
2.
Max. Speed
”
in operation with two control circuits.
Max. Speed ON
Motorheating
(12D)
Motorheating ON / OFF
Motorheating ON
Switch over direction
of rotation
(13D)
Reverse direction of rotation
“
right-hand
”
/
“
left-hand
”
(only for
frequency inverter with 3 ~ output)
Switch over direction of
rotation
Freeze function
14D
“
Freeze function
”
= maintain momentary modulation value
Modulation is retained
Override Time
(21D)
Do not use function for timer (only for digital input).
-
For mode speed controller
1.01
...
Setpoint1/2
(5D)
Switch over
“
Set Intern1
”
/
“
Set Intern2
”
“
Setting External 1
”
must be at
“
OFF
”
Set Intern2
Setpoint int./ext.
(6D)
Switch over
“
Intern
”
/
“
Extern
”
Set extern
For modes as controller (from
2.01.
)
Setpoint1/2
(5D)
Switch over
“
Setpoint 1
”
/
“
Setpoint 2
”
for control circuit1
Setpoint2
Setpoint int./ext.
(6D)
Switch over
“
Intern
”
/
“
Extern
”
Possible only for operation with one control circuit!
Setpoint External
Control/Manual
(7D)
Switch over
“
automatic control
”
/
“
Speed manual
”
Possible only for operation with one control circuit!
Manual mode
Heating/Cooling
(8D)
Switch over control function (e.g.
“
heating
”
/
“
cooling
”
)
Reversal standard
1.Setp+Pband1/2
(15D)
for control circuit 1: Switch over Setpoint 1/2 and Pband 1/1
When programming this function,
“
Setting
”
additionally lists
the parameter:
“
1.Pband2 for control circuit 1.
”
First control circuit Set-
point 2 + Pband 2
Only active in operation with a second control circuit!
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
95/123