9.11.2
Limit indication depending on setting or sensor signal
Same procedure for analogue inputs
“
E1
”
and
“
E2
”
.
Limits
Following functions can be allocated to the limit indication
OFF
Lmt E1 Function
OFF
none Function (factory setting)
Failure
(1L)
Limit alarm alternating with actual value display Is listed in the proto-
col as an alarm.
Indication with the centralized fault of a programmed relay (IO alloca-
tion Function
|
2K
|
).
Message
(2L)
Is listed in the protocol as a message. There is no alternating mes-
sage on the actual value display and no message via alarm relay.
Filter error
(3L)
Like function
|
1L
|
with fault message
“
Filter
”
Filter Message
(4L)
Like function
|
2L
|
with fault message
“
Filter
”
In the IO setup, a separate relay can be allocated independent of these settings.
Limits
Both values for E1 (
“
E1 min
”
and
“
E1 max
”
) can be set independent of each other and
act on a relay together if correspondingly programmed. If a function is activated or if a
relay is allocated, both settings (
“
min
”
and
“
max
”
) are initially at
“
OFF
”
.
Work can be carried out with one as well as with both limit indicators.
The same setting applies to
“
E2 Min.
”
and
“
E2 Max.
”
, described below for
“
E1
”
.
Undercutting the signal (
“
E1 min
”
).
If the signal undercuts the set value
“
E1 min
”
, this is reported until the set value (plus
adjustable hysteresis) has been exceeded once again.
Exceeding the signal (
“
E1 max
”
).
If the signal exceeds the set value
“
E1 max
”
, this is reported until the set value (minus
hysteresis) has been undercut once again.
- - - - -
Lmt E1 min
Limits
- - - - -
Lmt E1 max.
Limits
E1 Hysteresis
Hysteresis adjustment in the unit of measure of the programmed input signal.
- - - - -
Lmt E1 Hyst.
Limits
E1 Delay
Time delay exceeding
“
Level max.
”
up to indication by relay and alarm symbol.
Setting range: 0 - 120 sec.
Factory setting: 2 sec.
- - - - -
Lmt E1Del.
Information
Always adjust the value for the maximum input signal higher than the value for the minimum input
signal!
E1 Max. > E1 Min.
Example for a limit indication of default signal or sensor signal to
“
Analog In 1
”
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
86/123