9.0 mA
E1-Current
4.0 V
E1 - Voltage
20.0
°
C
E2 - KTY
E2
Signal height at analog input E2 (Analog In 2)
9.0 mA
E2-Current
4.0 V
E2 - Voltage
OFF
D1
D1
Status digital input 1 (Digital In 1)
ON = terminals D1 - D1 bridged
↔
OFF = terminals D1 - D1 not bridged
OFF
D2
D2
Status digital input 2 (Digital In 2)
ON = terminals D2 - D2 bridged
↔
OFF = terminals D2 - D2 not bridged
ON
K1
K1
OFF = relay K1 de-energized: terminals 11 - 12 bridged
ON = relay K1 energized: terminals 11 - 14 bridged
OFF
K2
K2
OFF = relay K2 de-energized: terminals 21 - 22 bridged
ON = relay K2 energized: terminals 21 - 24 bridged
11.1
Current measurements
Current measurements can be made without restrictions only on the motor side of the frequency
inverter or EC controller.
Line side measurements of the current may only be performed using true r.m.s. measuring equipment.
The line current cannot be measured with suf
fi
cient accuracy using customary measuring equipment
(for sinusoidal currents of corrected arithmetic mean).
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Diagnostics menu
L-BAL-E212-GB 1451 Index 003
Part.-No.
113/123