6.2 Tuning-less Function
6-13
6
Adjustm
e
nts
∗
Operate using S.
(3) Automatically Setting the Notch Filter
Usually, set this function to Auto Setting. (The notch filter is factory-set to Auto Setting.)
If this function is set to Auto Setting, vibration will be detected automatically and the notch filter will be set
when the tuning-less function is enabled.
Set this function to Not Auto Setting only if you do not change the notch filter setting before executing tuning-
less function.
(4) Tuning-less Level Settings
Two tuning-less levels are available: the rigidity level and load level. Both levels can be set in the Fn200 util-
ity function or in the Pn170 parameter.
Rigidity Level
a) Using the utility function
To change the setting, refer to
6.2.2 Tuning-less Levels Setting (Fn200) Procedure
.
b) Using the parameter
Gain switching
Not available
–
Offline moment of inertia calculation
*
Not available
Disable the tuning-less function by setting
Pn170.0 to 0 before executing this function.
Mechanical analysis
*
Available
While this function is being used, the tuning-
less function cannot be used. After
completion of the analysis, it can be used
again.
(cont’d)
Function
Availability
Remarks
Parameter
Meaning
When Enabled
Classification
Pn460
n. 0
Does not set the 2nd notch filter automatically with
utility function.
Immediately
Tuning
n. 1
[Factory setting]
Set the 2nd notch filter automatically with utility
function.
Digital Operator Display
Meaning
Level 0
Rigidity level 0
Level 1
Rigidity level 1
Level 2
Rigidity level 2
Level 3
Rigidity level 3
Level 4
[Factory setting]
Rigidity level 4
Parameter
Meaning
When Enabled
Classification
Pn170
n. 0
Rigidity level 0 (Level 0)
Immediately
Setup
n. 1
Rigidity level 1 (Level 1)
n. 2
Rigidity level 2 (Level 2)
n. 3
Rigidity level 3 (Level 3)
n. 4
[Factory setting]
Rigidity level 4 (Level 4)