5 Operation
5.8.5 Checking Output Torque Limiting during Operation
5-64
(2) Related Parameters
Set the following parameters for torque limit by external torque limit and analog voltage reference.
The setting unit is a percentage of the rated torque.
5.8.5
Checking Output Torque Limiting during Operation
The following signal can be output to indicate that the servomotor output torque is being limited.
Note: Use parameter Pn50F.0 to allocate the /CLT signal for use. For details, refer to
3.4.2 Output Signal Allocations
.
Pn400
Torque Reference Input Gain
Classification
Setting Range
Setting Unit
Factory Setting
When Enabled
Setup
10 to 100
0.1 V
30 (Rated torque at
3.0 V)
Immediately
Pn402
Forward Torque Limit
Classification
Setting Range
Setting Unit
Factory Setting
When Enabled
Setup
0 to 800
1%
800
Immediately
Pn403
Reverse Torque Limit
Classification
Setting Range
Setting Unit
Factory Setting
When Enabled
Setup
0 to 800
1%
800
Immediately
Pn404
Forward External Torque Limit
Classification
Setting Range
Setting Unit
Factory Setting
When Enabled
Setup
0 to 800
1%
100
Immediately
Pn405
Reverse External Torque Limit
Classification
Setting Range
Setting Unit
Factory Setting
When Enabled
Setup
0 to 800
1%
100
Immediately
Pn415
T-REF Filter Time Constant
Classification
Setting Range
Setting Unit
Factory Setting
When Enabled
0 to 65535
0.01 ms
0
Immediately
Setup
Speed
Position
Torque
Speed
Position
Torque
Speed
Position
Torque
Speed
Position
Torque
Speed
Position
Torque
Speed
Position
Torque
Type
Signal Name
Connector
Pin Number
Setting
Meaning
Output
/CLT
Must be allocated
ON (closed)
Servomotor output torque is being lim-
ited.
OFF (open)
Servomotor output torque is not being
limited.