Mini type VFD of CV20 series 

Thank you for using CV20 series Variable Frequency Drive made by Kinco Automation. 

CV20 satisfies the high performance requirements by using a unique control method to achieve high 

torque,  high  accuracy  and  wide  speed-adjusting  range.  Its  anti-tripping  function  and  capabilities  of 

adapting  to  severe  power  network,  temperature,  humidity  and  dusty  environment  exceed  those  of 
similar  product  made  by  other  companies,  which  improves  the  product’s  reliability 

noticeably;Without  PG  connector,  strong  speed  control,  flexible  input/output  terminal,  pulse 

frequency setting, saving parameters at power outage and stop, frequency setting channel, master and 

slave  frequency  control  and  so  on,  all  these  satisfy  various  of  high  accuracy  and  complex  drive 

command,  at  the  same  time  we  provide  the  OEM  customer  high  integration  total  solution,  it  values 

highly in system cost saving and improving the system reliability. 

  CV20 can satisfy the customers’ requirements on low noise and EMI by using optimized PWM 

technology and EMC design. 

 

This  manual  provides  information  on  installation,  wiring,  parameters  setting,  trouble-shooting, 

and  daily  maintenance.  To  ensure  the  correct  installation  and  operation  of  CV20,  please  read  this 

manual carefully before starting the drive and keep it in a proper place and to the right person. 

Unpacking Inspection Note 

Upon unpacking, please check for: 

 

Any damage occurred during transportation; 

 

Check whether the rated values on the nameplate of the drive are in accordance with your order. 

Our product is manufactured and packed at factory with great care. If there is any error, please contact 

us or distributors. 

The user manual is subject to change without notifying the customers due to the continuous process 

of product improvements 

VFD model rule   

 

CV20 – 4T– XXXXG–U–000 

 

 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

Production introduction:   

General specifications 

Item 

Description 

Input 

Rated voltage and 

frequency 

4T:3-phase,380V~440V AC; 50Hz/60Hz 

2S:Single-phase,200V~240V;50Hz/60Hz 

1S:Single-phase, 100~120V; 50/60HZ 

Allowable voltage 

range 

4T: 320V~460V AC;2S:180V~260V; 1S: 90~132V 

Voltage tolerance

3%; Frequency: ±5% 

Output 

Rated voltage 

4T:0~440V

2S:0~240V

1S:0~240V 

Frequency 

0Hz~300Hz (0~800HZ customizable) 

Overload capacity 

G type: 150% rated current for 1 minute, 180% rated 

current for 10 seconds; 

Control 

Characteristics 

Control mode 

V/F control   

Modulation mode 

Space vector PWM modulation 

Starting torque 

1 Hz 150%rated torque 

Frequency accuracy 

Digital setting: Max frequency ×±0.01%; 

Analog setting: Max. frequency ×±0.2% 

Frequency resolution 

Digital setting: 0.01Hz; 

Analog setting: Max frequency×0.1% 

Torque boost 

Manual torque boost :0%~30.0% 

V/F pattern 

4 patterns: 1 V/F curve mode set by user and   

3  kinds  of  torque-derating  modes  (2.0  order, 1.7  order,  and 

1.2 order) 

Acc/Dec curve 

Linear acceleration/deceleration,   

Four kinds of acceleration/deceleration time 

Auto current limit 

Limit current during the operation automatically 

to prevent frequent overcurrent trip 

Operation 

Function 

Operation Command 

Operation Panel, Terminal, CommunicationControl,   

Supportswitching between these control channesl. 

Frequency Setting 

Digital, Analog Voltage/current setting. 

Auxiliary frequency 

Support main and auxiliary setting(“+”,”-”, “min”, “max”) 

Operation panel 

LED Display 

Display setting frequency, output frequency, output voltage, 

output current and so on, about 20 parameters. 

Keys lock and 

function selection 

Lock part of keys or all the keys.   

Define the function of part of keys 

Item 

Description 

Protection function 

Open  phase  protection  (optional),  overcurrent  protection, 

overvoltage  protection,  under-voltage  protection,  overheat 

protection, over-load protection and so on. 

Environment 

Operating site 

Indoor, installed in the environment free from 

directsunlight, dust, corrosive gas, combustible gas, oil 

mist, steam and drip. 

Altitude 

Derated above 1000m, the rated output current   

shall be decreased by 10% for every rise of 1000m 

Ambient temperature 

-10

~40

, derated at 40

~ 50

 

Humidity 

5%~95%RH, non-condensing 

Vibration 

Less than 5.9m/s2 (0.6g) 

Storage temperature 

40

~

70

 

Structure 

Protection class 

IP20 

Cooling method 

Air cooling, with fan control. 

Installation method 

Wall-mounted 

Efficiency 

≥90% 

Introduction of CV20 series: 

Model of VFD 

Rated capacity

kVA

 

Rated input 

current

A

 

Rated output 

current

A

 

Motor power 

kW

 

CV20-1S-0002G 

0.6 

6.0 

1.3 

0.2 

CV20-1S-0004G 

1.0 

9.0 

2.5 

0.4 

CV20-1S-0007G 

1.5 

18.0 

4.0 

0.75 

CV20-2S-0004G 

1.0 

5.3 

2.5 

0.4 

CV20-2S-0007G 

1.5 

8.2 

4.0 

0.75 

CV20-2S-0015G 

3.0 

14.0 

7.5 

1.5 

CV20-4T-0007G 

1.5 

3.4 

2.3 

0.75 

CV20-4T-0015G 

3.0 

5.0 

3.7 

1.5 

CV20-4T-0022G 

4.0 

5.8 

5.5 

2.2 

External dimension: 

 

CV20-2S-0004G~ CV20-2S-0015G/ CV20-1S-0002G~ CV20-1S-0007G 

 

CV20-4T-0007G~CV20-4T-0022G 

Mechanical parameters 

VFD model 

G: Constant torque load; 

L: Draught fan and water 

pump load

 

External dimension and (mm) 

Weight 

(kg) 

W1 

H1 

D1 

T1 

Installa-

tion 

hole(d) 

CV20-1S-0002G 

68 

132 

131 

56 

120 

12 

0.8 

CV20-1S-0004G 

CV20-1S-0007G 

CV20-2S-0004G 

CV20-2S-0007G 

CV20-2S-0015G 

CV20-4T-0007G 

100 

151 

128 

89 

140 

1.0 

CV20-4T-0015G 

CV20-4T-0022G 

Operation Button Description 

Button 

Description 

 

Increase the value or function

 

 

Decrease the value or function

 

MENU 

Enter or Exit the programming status

 

RUN / 

STOP 

In panel operation mode, run the vfd by the first pressing; stop vfd by the second   

pressing. In VFD error status, reset the error by pressing

 

SHIFT / 

ENTER 

Short pressing to shift data or function code. Hold pressing(more than 1s) to enter 

function code or save the changed value

 

Wiring:

 

  Danger 

-Wiring can only be done after the drive’s AC power is disconnected, all the LEDs on the operation 

panel are off and waiting for at least 5 minutes. Then, you can remove the panel. 

-Wiring job can only be done after confirming the charge indicator on the right bottom is off and the 

voltage between main circuit power ter and - is below DC36V. 

-Wire connections can only be done by trained and authorized person 

-Check the wiring carefully before connecting emergency stop or safety circuits. 

-Check the drive’s voltage level before supplying power to it, otherwise human injuries or equipment 

damage may happen. 

Attention     

-Check  whether  the  Variable  Speed  Drive’s  rated  input  voltage  is  in  compliant  with  the  AC  supply 

voltage before using. 

-Dielectric strength test of the drive has been done in factory, so you need not do it again. 

-Refer to chapter 2 on connected braking resistor or braking kit. 

-It is prohibited to connect the AC supply cables to the drive’s terminals U, V and W. 

-Grounding cables should be copper cables with section area bigger than 3.5mm2, and the grounding 
resistance should be less than 10Ω. 

-There is leakage current inside the drive. The total leakage current is greater than 3.5mA, depending 

on  the  usage  conditions.  To  ensure  safety,  both  the  drive  and  the  motor  should  be  grounded,  and  a 

leakage  current  protector  (RCD)  should  be  installed.  It  is  recommended  to  choose  B  type RCD  and 

set the leakage current at 300mA. 

-The drive should be connected to the AC supply via a circuit breaker or fuse to provide convenience 

to input over-current protection and maintenance. 

 

R/L1 

S/L2 

T/L3 

 

 

U/L1 

V/L2 

W/L3 

 

 

Terminal name 

Function description 

R/L1

S/L2

T/L3 

Single-phase 220V(R/L1, S/L2) or 3-phase 380VAC input terminal 

U/T1

V/T2

W/T3 

3-phase AC output terminal 

 

Shield terminal 

 

Main loop

Control loop

R/L1
S/L2

T/L3
PE

U/T1
V/T2

W/T3

X1
X2
X3
X4

COM

+10V

AI

COM

PE

Ra

Rc

1

3

I

V

AI1

M

Multi-function input 1

Multi-function input 2

Multi-function input 3

Multi-function input 4

Analog input

Programable relay output

3-Phase AC power

Braker

PE for motor

Modbus rtu

RS485

2:+5v

  3:485+

 4:485-

  5:GND

×

Note: DIP 

switch setting

 

Arrangement of control circuit terminals is as follows: 

 

RA 

RC 

+10V 

A1 

X1 

X2 

X3 

X4 

COM 

 

It lists the possible faults of CV20. The fault code varies from E001 to E027. Once a fault occurs, you 

may  check  it  against  the  table  and  record  the  detailed  phenomena  before  seeking  service  from  your 

supplier. 

Faults and actions 

Fault 

code 

Fault 

categories   

Possible reasons for fault 

Actions 

E001 

Over-current 

during 

acceleration 

Acc time is too short 

Prolong the Acc time 

Parameters of motor are wrong 

Auto-tune the parameters of 

motor 

Coded disc breaks down, when 

PG is running 

Check the coded disc and the 

connection 

Drive power is too small 

Select a higher power drive 

V/F curve is not suitable 

Check and adjust V/F curve, 

adjust torque boost 

E002 

Over-current   

during   

deceleration 

Deceleration time is too short 

Prolong the Dec time 

The load generates energy or 

the load inertial is too big 

Connect suitable braking kit 

Coded disc breaks down, when 

PG is running 

Check the coded disc and the 

connection 

Drive power is too small 

Select a higher power drive 

E003 

Over-current 

in 

constant speed 

operation 

Acceleration /Deceleration 

time is too short 

Prolong Acceleration/ 

Deceleration time 

Sudden change of load or 

Abnormal load 

Check the load 

Low AC supply voltage 

Check the AC supply voltage 

Coded disc breaks down, when 

PG is running 

Check the coded disc and the 

connection 

Drive power is too small 

Select a higher power drive 

E004 

Over voltage   

during   

acceleration 

Abnormal AC supply voltage 

Check the power supply 

Too short acceleration time 

Prolong acceleration time 

E005 

Over voltage 

during 

deceleration 

Too short Deceleration time 
(with reference to generated 

energy) 

Prolong the deceleration time 

The load generates energy or 

the load inertial is too big 

Connect suitable braking kit 

E006 

Over voltage 

in   

constant-speed   

operating   

process 

Wrong ASR parameters, when 

drive run in the vector control 

mode   

Refer to A5. ASR parameter 

setting 

Acceleration /Deceleration 

time is too short 

Prolong Acceleration/ 

Deceleration time 

Abnormal AC supply voltage 

Check the power supply 

Abnormal change of input 

voltage 

Install input reactor 

Too big load inertia 

Connect suitable braking kit 

E007 

Drive’s 

control power 

supply over 

voltage 

Abnormal AC supply voltage 

Check the AC supply voltage or 

seek service 

E008 

Input phase 

loss   

Any of phase R, S and T 

cannot be detected 

Check the wiring and installation   

Check the AC supply voltage 

E009 

Output phase 

loss 

Any of Phase U, V and W 

cannot be detected 

Check the drive’s output wiring 

Check the cable and the motor 

E010 

Protections of 

IGBT act 

Short-circuit among 3-phase 

output or line-to-ground short 

circuit 

Rewiring, please make sure the 

insulation of motor is good 

Instantaneous over-current 

Refer to E001~E003 

Vent is obstructed or fan does 

not work 

Clean the vent or replace the fan 

Over-temperature 

Lower the ambient temperature 

Wires or connectors of control 

board are loose 

Check and rewiring 

Current waveform distorted 

due to output phase loss 

Check the wiring 

Auxiliary power supply is 
damaged or IGBT driving 

voltage is too low 

Seek service 

Short-circuit of IGBT bridge 

Seek service 

Control board is abnormal 

Seek service 

E011 

IGBT 

module’s   

heatsink 

overheat 

Ambient over-temperature 

Lower the ambient temperature 

Vent is obstructed   

Clean the vent 

Fan does not work 

Replace the fan 

IGBT module is abnormal 

Seek service 

E012 

Rectifier’s 

heatsink 
overheat 

Ambient over-temperature 

Lower the ambient temperature 

Vent is obstructed   

Clean the vent 

Fan does not work 

Replace the fan 

!

Reserved 

VFD code 
CV: Mini type 

Communication port:   
None: Standard RS485 
A: CAN 

The second generation 

Power 
0002: 200w 
0004: 400w 
0015: 1.5kw 
…… 

Power supply 
1

100V 

2

200V 

4

400V 

 
 
4: 400V 

00: Standard model 
…..other models 

S: Signal phase 
T: Three-phase 

G: Constant torque 
L: Constant power 

Top of single-phase/3-phase   

 

Bottom   

 

RS-485 