Fault
code
Fault
categories
Possible reasons for fault
Actions
E013
Drive
overload
Parameters of motor are wrong
Auto-tune the parameters of
motor
Too heavy load
Select the drive with bigger
power
DC injection braking current is
too big
Reduce the DC injection braking
current and prolong the braking
time
Too short acceleration time
Prolong acceleration time
Low AC supply voltage
Check the AC supply voltage
Improper V/F curve
Adjust V/F curve or torque boost
value
E014
Motor
over-load
Improper motor’s overload
protection threshold
Modify the motor’s overload
protection threshold.
Motor is locked or load
suddenly become too big
Check the load
Common motor has operated
with heavy load at low speed
for a long time.
Use a special motor if the motor
is required to operate for a long
time.
Low AC supply voltage
Check the AC supply voltage
Improper V/F curve
Set V/F curve and torque boost
value correctly
E015
external
equipment
fails
Terminal used for stopping the
drive in emergent status is
closed
Disconnect the terminal if the
external fault is cleared
E016
EEPROM
R/W fault
R/W fault of control
parameters
Press STOP/RST to reset, seek
service
E017
Communicatio
n timeout
The setting time is too shot
Set b3.02 to 0, it means do not
detection
E018
Contactor not
closed
Low AC supply voltage
Check the AC supply voltage
Contactor damaged
Replace the contactor in main
circuit and seek service
Soft start resistor is damaged
Replace the soft start resistor and
seek service
Control circuit is damaged
Seek service
Input phase loss
Check the wiring of R, S, T.
E019
Current
detection
circuit
fails
Wires or connectors of control
board are loose
Check and re-wire
Auxiliary power supply is
damaged
Seek service
Hall sensor is damaged
Seek service
Amplifying circuit is abnormal
Seek service
E020
System
interference
Terrible interference
Press
STOP/RST
key to reset or
add a power filter in front of
power supply input
DSP in control board
read/write by mistake
Press
STOP/RST
key or seek
service.
E023
Parameter
copy
error
Panel’s parameters are not
complete or the version of the
parameters are not the same as
that of the main control board
Update the panel’s parameters
and version again. First set b4.04
to 1 to upload the parameters and
then set b4.04 to 2 or 3 to
download the parameters.
Panel’s EEPROM is damaged
Seek service
E024
Auto-tuning
fault
Improper settings of
parameters on the nameplate
Set the parameters correctly
according to the nameplate
Prohibiting contra
Auto-turning during rollback
Cancel prohibiting rollback
Overtime of auto-tuning
Check the motor’s wiring
Check the set value of
A0.10(upper limiting frequency),
make sure if it is lower than the
rated frequency or not
E026
The load of
drive is lost
The load is lost or reduced
Check the situation of the load
E027
Brake unit
fault
Brake tube is broken
Seek service
List of Parameters:
Function
code
Name
Descriptions
Unit
Factory
setting
Modif
Setting
range
Group A0
:
Basic operating parameters
A0.00
User password
0: No password protection.
Others:Password
protection.
1
0
○
0~FFFF
A0.01
Control mode
0~1: reserved
2: V/F control
1
0
×
0~2
A0.02
Main reference
frequency selector
0: Digital setting in A0.03
1: AI
2: Reserved
3:Potentiometer
1
3
○
0~5
Function
code
Name
Descriptions
Unit
Factory
setting
Modif
Setting
range
A0.03
Set the operating
frequency in digital
mode
A0.11~A0.10
0.01 Hz
50.00
○
0~3000
A0.04
Methods of
inputtingoperating
commands
0: Panel control
1: Terminal control
2: Communication control
1
0
○
0~2
A0.05
Set running
direction
0: Forward
1: Reverse
1
0
○
0~1
A0.06
Acc time 1
0.0~6000.0
0.1s
6.0s
○
0~60000
A0.07
Dec time 1
0.0~6000.0
0.1s
6.0s
○
0~60000
A0.08
Max. output
frequency
50Hz~ 300.00Hz
0.01Hz
50.00
×
0~30000
A0.09
Max. output
voltage
0~480
1V
VFD’s
rated
values
×
0~480
A0.10
Upper limit of
frequency
A0.11~A0.08
0.01Hz
50.00
○
0~30000
A0.11
Lower limit of
frequency
0.00~A0.10
0.01Hz
0.00
○
0~30000
A0.12
Basic operating
frequency
0.00~300.00Hz
0.01Hz
50.00
○
0~30000
A0.13
Torque boost
0.0%(Auto),0.1%~30.0%
0.1%
0.0%
○
0~300
Group A1: Start and stop parameters
A1.00
Starting mode
0: Start from the starting
frequency
1: Brake first and then start
2: Reserved
1
0
×
0~2
A1.01
Starting frequency
0.00~60.00Hz
0.01Hz
0.00Hz
○
0~6000
A1.02
Holding time of
starting frequency
0.00~10.00s
0.01s
0.00s
○
0~1000
A1.03
DC injection
braking current at
start
0.0%~100.0% drive’s rated
current
0.1%
0.0%
○
0~1000
A1.04
DC injection
braking time at
start
0.00
(
No action
)
0.01~30.00s
0.01s
0.00s
○
0~3000
A1.05
Stopping mode
0: Dec-to-stop
1: Coast-to-stop
2: Dec-to-stop+DC
injection braking
1
0
×
0~2
A1.06
DC injection
braking initial
frequency at stop
0.00~60.00Hz
0.01Hz
0.00Hz
○
0~6000
A1.07
Injection braking
waiting time at
stop
0.00~10.00s
0.01s
0.00s
○
0~1000
A1.08
DC injection
braking current at
stop
0.0%~100.0% drive’s rated
current
0.1%
0.0%
○
0~1000
A1.09
DC injection
braking time at
stop
0.0
(
No action
)
0.01~30.00s
0.01s
0.00s
○
0~3000
A1.10
Restart after power
failure
0:Disable
1:Enable
1
0
×
0~1
A1.11
Delay time for
restart after power
failure
0.0~10.0s
0.1s
0.0s
○
0~100
A1.12
Anti-reverse
running function
0: Disabled
1: Enabled (It will operate
at zero frequency when
input a reverse command)
1
0
×
0~1
A1.13
Delay time of run
reverse/ forward
0.00~360.00s
0.01s
0.00s
○
0~36000
A1.14
Switch mode of
run reverse/
forward (Reserved)
0: Switch when pass 0Hz
1: Switch when pass
starting frequency
1
0
×
0~1
A1.15
Detecting
frequency of stop
0.00~150.00Hz
0.01Hz
0.10Hz
×
0~15000
A1.16
Reserved
Group A2
:
Frequency setting
A2.00
Auxiliary reference
frequency selector
0: No auxiliary reference
frequency
1: AI
5: Output by PID process
1
0
○
0~5
A2.01
Main and auxiliary
reference
frequency
calculation
0: +
1: -
2: MAX (Main reference,
Auxiliary reference)
3: MIN (Main reference,
Auxiliary reference)
1
0
○
0~3
A2.02
UP/DN rate
0.01~99.99Hz/s
0.01
1.00
○
1~9999
A2.03
UP/DN regulating
control
Unit’s place of LED:
0:Save reference frequency
upon power outage
1:Not save reference
frequency upon power
outage.
Ten’s place of LED:
0:Hold reference frequency
at stop
1:Clear reference
frequency at stop
Hundred’s place of LED:
1
00
○
0~11H
Function
code
Name
Descriptions
Unit
Factory
setting
Modif
Setting
range
0:UP/DN integral time
valid
1:UP/DN speed value
A2.04
Jog operating
frequency
0.10~50.00Hz
0.01Hz
5.00
○
10~5000
A2.05
Interval of Jog
operation
0.0~100.0s
0.1s
0.0
○
0~1000
A2.06
Skip frequency 1
0.00~300.00Hz
0.01Hz
0.00
×
0~30000
A2.07
Range of skip
frequency 1
0.00~30.00Hz
0.01Hz
0.00
×
0~3000
A2.08
Skip frequency 2
0.00~300.00Hz
0.01Hz
0.00
×
0~30000
A2.09
Range of skip
frequency
0.00~30.00Hz
0.01Hz
0.00
×
0~3000
A2.10
Skip frequency 3
0.00~300.00Hz
0.01Hz
0.00
×
0~30000
A2.11
Range of skip
frequency 3
0.00~30.00Hz
0.01Hz
0.00
×
0~3000
Group A3:Setting curve
A3.00
Reference
frequency
curve selection
LED unit’s place:
AI curve selection
0: Curve 1
1: Curve 2
2: Curve 3
3: Curve 4
1
3330
○
0~3333H
A3.01
Max reference of
curve 1
A3.03~110.00%
0.01%
100.00%
○
0~11000
A3.02
Actual value
Corresponding to
the Max reference
of curve 1
Reference frequency:
0.0~100.00%Fmax
Torque: 0.0~300.00%Te
0.01%
100.00%
○
0~10000
A3.03
Min reference of
curve 1
0.0%~A3.01
0.01%
0.00%
○
0~11000
A3.04
Actual value
Corresponding to
the Min reference
of curve 1
The same as A3.02
0.01%
0.00%
○
0~10000
A3.05
Max reference of
curve 2
A3.07~110.00%
0.01%
100.00%
○
0~11000
A3.06
Actual value
corresponding to
the Max reference
of curve 2
The same as A3.02
0.01%
100.00%
○
0~10000
A3.07
Min reference of
curve 2
0.0%~A3.05
0.01%
0.00%
○
0~11000
A3.08
Actual value
Corresponding to
the Min reference
of curve 2
The same as A3.02
0.01%
0.00%
○
0~10000
A3.09
Max reference of
curve 3
A3.11~110.00%
0.01%
100.00%
○
0~11000
A3.10
Actual value
Corresponding to
the Max reference
of curve 3
The same as A3.02
0.01%
100.00%
○
0~10000
A3.11
Min reference of
curve 3
0.0%~A3.09
0.01%
0.00%
○
0~11000
A3.12
Actual value
corresponding to
the Min reference
of curve 3
The same as A3.02
0.01%
0.00%
○
0~10000
A3.13
Max reference of
curve 4
A3.15~110.00%
0.01%
100.00%
○
0~11000
A3.14
Actual value
corresponding to
the Max reference
of curve 4
The same as A3.02
0.01%
100.00%
○
0~10000
A3.15
Reference of
inflection point 2
of curve 4
A3.17~A3.13
0.01%
100.00%
○
0~11000
A3.16
Actual value
corresponding to
the Min reference
of inflection point
2 of curve 4
The same as A3.02
0.01%
100.00%
○
0~10000
A3.17
Reference of
inflection point 1
of curve 4
A3.19~A3.15
0.01%
0.00%
○
0~11000
A3.18
Actual value
corresponding to
the Min reference
of inflection point
1 of curve 4
The same as A3.02
0.01%
0.00%
○
0~10000
A3.19
Min reference of
curve 4
0.0%~A3.17
0.01%
0.00%
○
0~11000
A3.20
Actual value
corresponding to
the Min reference
of curve 4
The same as A3.02
0.01%
0.00%
○
0~10000
Group A4
:
Acc/Dec parameters
A4.00
Acc/Dec mode
0: Linear Acc/Dec
1: S Curve
1
0
×
0~1
A4.01
Acc time 2
0.0~6000.0
0.1 s
20.0 s
○
0~60000
A4.02
Dec time 2
0.0~6000.0
0.1 s
20.0 s
○
0~60000
A4.03
Acc time 3
0.0~6000.0
0.1 s
20.0 s
○
0~60000
Function
code
Name
Descriptions
Unit
Factory
setting
Modif
Setting
range
A4.04
Dec time 3
0.0~6000.0
0.1 s
20.0 s
○
0~60000
A4.05
Acc time 4
0.0~6000.0
0.1 s
20.0 s
○
0~60000
A4.06
Dec time 4
0.0~6000.0
0.1 s
20.0 s
○
0~60000
A4.07
S curve
acceleration
starting time
10.0%~50.0%(Acc time)
A4.07+ A4.08≤90%
0.1%
20.0%
○
100~500
A4.08
S curve
acceleration ending
time
10.0%~70.0%(Acc time)
A4.07+ A4.08≤90%
0.1%
20.0%
○
100~800
A4.09
S curve
deceleration
starting time
10.0%~50.0%(Dec time)
A4.09+ A4.10≤90%
0.1%
20.0%
○
100~500
A4.10
S curve
deceleration
ending time
10.0%~70.0%(Dec time)
A4.09+ A4.10≤90%
0.1%
20.0%
○
100~800
A4.11
Quick start-stop
selector
0: Disable
1: Quick start,normal stop
2: Normal start,quick stop
3: Quick start,quick stop
1
2
×
0~3
A4.12
Start ACR-P
0.1~200.0
0.1
20.0
○
1~2000
A4.13
Start ACR-I
0.000~10.000s
0.001 s
0.200s
○
0~10000
A4.14
Start AVR-P
0.1~200.0
0.1
20.0
○
1~2000
A4.15
Start AVR-I
0.000~10.000s
0.001 s
0.200s
○
0~10000
A4.16
Stop ACR-P
0.1~200.0
0.1
20.0
○
1~2000
A4.17
Stop ACR-I
0.000~10.000s
0.001 s
0.200s
○
0~10000
A4.18
Stop AVR-P
0.1~200.0
0.1
20.0
○
1~2000
A4.19
Stop AVR-I
0.000~10.000s
0.001 s
0.200s
○
0~10000
A4.20
Over
Commtatation Stop
0: disable
1:enable
1
0
×
0~1
A4.21
ACC/DEC time
coefficient
0:ACC/DEC time × 1
1: ACC/DEC time × 0.1
1
0
×
0~1
A4.22
ACC/DEC time
1/2 switch freq.
0.00~300.00Hz
Select ACC/DEC time 2
when output freq. is less
than A4.22
0.01Hz
0.00Hz
×
0~30000
A4.23~
A4.40
Reserved
Reserved
1
0
○
0~65535
Group A5
:
reserved
Group A6
:
Control terminals parameters
A6.00~
A6.03
Multi-function
terminal X1~X4
0: No function1:Forward
2: Reverse
3: Forward jog operation
4: Reverse jog operation
5: 3-wire operation control
6: External RESET signal
input
7: External fault signal
input
8: External interrupt signal
input
9: Drive operation prohibit
10: External stop command
11: DC injection braking
command
12: Coast to stop
13: Frequency ramp up
(UP)
14: Frequency ramp down
(DN)
15: Switch to panel control
16: Switch to terminal
control
17: Switch to
communication control
mode
18: Main reference
frequency via AI
27: Preset frequency 1
28: Preset frequency 2
29: Preset frequency 3
30: Preset frequency 4
31: Acc/Dec time 1
32: Acc/Dec time 2
33: Multiple close-loop
reference selection 1
34: Multiple close-loop
reference selection 2
35: Multiple close-loop
reference selection 3
36: Multiple close-loop
reference selection 4
37: Forward prohibit
38: Reverse prohibit
39: Acc/Dec prohibit
40: Process close-loop
prohibit
42: Main frequency switch
to digital setting
43: PLC pause
44: PLC prohibit
45: PLC stop memory clear
46: Swing input
47: Swing reset
1
0
×
0~54