Fault 

code 

Fault 

categories   

Possible reasons for fault 

Actions 

E013 

Drive 

overload 

Parameters of motor are wrong 

Auto-tune the parameters of 

motor 

Too heavy load 

Select the drive with bigger 

power 

DC injection braking current is 

too big 

Reduce the DC injection braking 

current and prolong the braking 

time   

Too short acceleration time 

Prolong acceleration time 

Low AC supply voltage 

Check the AC supply voltage 

Improper V/F curve 

Adjust V/F curve or torque boost 

value 

E014 

Motor 

over-load 

Improper motor’s overload 

protection threshold 

Modify the motor’s overload 

protection threshold. 

Motor is locked or load 

suddenly become too big 

Check the load 

Common motor has operated 
with heavy load at low speed 

for a long time. 

Use a special motor if the motor 

is required to operate for a long 

time. 

Low AC supply voltage 

Check the AC supply voltage 

Improper V/F curve 

Set V/F curve and torque boost 

value correctly 

E015 

external   

equipment 

fails 

Terminal used for stopping the 

drive in emergent status is 

closed 

Disconnect the terminal if the 

external fault is cleared 

E016 

EEPROM 
R/W fault 

R/W fault of control 

parameters 

Press STOP/RST to reset, seek 

service 

E017 

Communicatio

n timeout 

The setting time is too shot 

Set b3.02 to 0, it means do not 

detection 

E018 

Contactor not   

closed 

Low AC supply voltage 

Check the AC supply voltage 

Contactor damaged 

Replace the contactor in main 

circuit and seek service 

Soft start resistor is damaged 

Replace the soft start resistor and 

seek service 

Control circuit is damaged 

Seek service 

Input phase loss 

Check the wiring of R, S, T. 

E019 

Current   

detection 

circuit   

fails 

Wires or connectors of control 

board are loose 

Check and re-wire 

Auxiliary power supply is 

damaged   

Seek service 

Hall sensor is damaged 

Seek service 

Amplifying circuit is abnormal 

Seek service 

E020 

System 

interference 

Terrible interference 

Press 

STOP/RST

key to reset or 

add a power filter in front of 

power supply input 

DSP in control board 

read/write by mistake 

Press 

STOP/RST

 key or seek 

service. 

E023 

Parameter 

copy   

error 

Panel’s parameters are not 

complete or the version of the 

parameters are not the same as 

that of the main control board   

Update the panel’s parameters 

and version again. First set b4.04 
to 1 to upload the parameters and 

then set b4.04 to 2 or 3 to 
download the parameters. 

Panel’s EEPROM is damaged 

Seek service 

E024 

Auto-tuning 

fault 

Improper settings of 

parameters on the nameplate 

Set the parameters correctly 

according to the nameplate 

Prohibiting contra 

Auto-turning during rollback 

Cancel prohibiting rollback 

Overtime of auto-tuning 

Check the motor’s wiring 

Check the set value of 

A0.10(upper limiting frequency), 

make sure if it is lower than the 

rated frequency or not 

E026 

The load of 
drive is lost 

The load is lost or reduced 

Check the situation of the load 

E027 

Brake unit 

fault 

Brake tube is broken 

Seek service 

 

List of Parameters: 

Function

 

code 

Name 

Descriptions 

Unit 

Factory 

setting 

Modif 

Setting 

range 

Group A0

Basic operating parameters 

A0.00 

User password 

0: No password protection. 
Others:Password 
protection. 

○ 

0~FFFF 

A0.01 

Control mode 

0~1: reserved 
2: V/F control 

× 

0~2 

A0.02 

Main reference   
frequency selector 

0: Digital setting in A0.03 
1: AI 
2: Reserved 
3:Potentiometer 

○ 

0~5 

Function

 

code 

Name 

Descriptions 

Unit 

Factory 

setting 

Modif 

Setting 

range 

A0.03 

Set the operating   
frequency in digital 
mode 

A0.11~A0.10 

0.01 Hz 

50.00 

○ 

0~3000 

A0.04 

Methods of 
inputtingoperating 
commands 

0: Panel control 
1: Terminal control 
2: Communication control 

○ 

0~2 

A0.05 

Set running   
direction 

0: Forward   
1: Reverse 

○ 

0~1 

A0.06 

Acc time 1 

0.0~6000.0 

0.1s 

6.0s 

○ 

0~60000 

A0.07 

Dec time 1 

0.0~6000.0 

0.1s 

6.0s 

○ 

0~60000 

A0.08 

Max. output   
frequency 

50Hz~ 300.00Hz 

0.01Hz 

50.00 

× 

0~30000 

A0.09 

Max. output   
voltage 

0~480 

1V 

VFD’s 

rated 

values 

× 

0~480 

A0.10 

Upper limit of 
frequency 

A0.11~A0.08 

0.01Hz 

50.00 

○ 

0~30000 

A0.11 

Lower limit of 
frequency 

0.00~A0.10 

0.01Hz 

0.00 

○ 

0~30000 

A0.12 

Basic operating     
frequency 

0.00~300.00Hz 

0.01Hz 

50.00 

○ 

0~30000 

A0.13 

Torque boost 

0.0%(Auto),0.1%~30.0% 

0.1% 

0.0% 

○ 

0~300 

Group   A1: Start and stop parameters 

A1.00 

Starting mode 

0: Start from the starting 
frequency 
1: Brake first and then start 
2: Reserved 

× 

0~2 

A1.01 

Starting frequency 

0.00~60.00Hz 

0.01Hz 

0.00Hz 

○ 

0~6000 

A1.02 

Holding time of 
starting frequency 

0.00~10.00s 

0.01s 

0.00s 

○ 

0~1000 

A1.03 

DC injection 
braking current at 
start 

0.0%~100.0% drive’s rated 
current 

0.1% 

0.0% 

○ 

0~1000 

A1.04 

DC injection 
braking time at 
start 

0.00

No action

 

0.01~30.00s 

0.01s 

0.00s 

○ 

0~3000 

A1.05 

Stopping mode 

0: Dec-to-stop 
1: Coast-to-stop 
2: Dec-to-stop+DC 
injection braking 

× 

0~2 

A1.06 

DC injection 
braking initial 
frequency at stop 

0.00~60.00Hz 

0.01Hz 

0.00Hz 

○ 

0~6000 

A1.07 

Injection braking 
waiting time at 
stop 

0.00~10.00s 

0.01s 

0.00s 

○ 

0~1000 

A1.08 

DC injection 
braking current at 
stop 

0.0%~100.0% drive’s rated 
current 

0.1% 

0.0% 

○ 

0~1000 

A1.09 

DC injection 
braking time at 
stop 

0.0

No action

 

0.01~30.00s 

0.01s 

0.00s 

○ 

0~3000 

A1.10 

Restart after power 
failure 

0:Disable 
1:Enable 

× 

0~1 

A1.11 

Delay time for 
restart after power 
failure 

0.0~10.0s 

0.1s 

0.0s 

○ 

0~100 

A1.12 

Anti-reverse 
running function 

0: Disabled 
1: Enabled (It will operate 
at zero frequency when 
input a reverse command) 

× 

0~1 

A1.13 

Delay time of run 
reverse/ forward 

0.00~360.00s 

0.01s 

0.00s 

○ 

0~36000 

A1.14 

Switch mode of 
run reverse/ 
forward (Reserved) 

0: Switch when pass 0Hz 
1: Switch when pass 
starting frequency 

× 

0~1 

A1.15 

Detecting 
frequency of stop 

0.00~150.00Hz 

0.01Hz 

0.10Hz 

× 

0~15000 

A1.16 

Reserved 

 

 

 

 

 

Group A2

Frequency setting 

A2.00 

Auxiliary reference   
frequency selector 

0: No auxiliary reference 
frequency 
1: AI 
5: Output by PID process 

○ 

0~5 

A2.01 

Main and auxiliary 
reference 
frequency 
calculation 

0: + 
1: - 
2: MAX (Main reference, 
Auxiliary reference) 
3: MIN (Main reference, 
Auxiliary reference) 

○ 

0~3 

A2.02 

UP/DN rate 

0.01~99.99Hz/s 

0.01 

1.00 

○ 

1~9999 

A2.03 

UP/DN regulating 
control 

Unit’s place of LED:   
0:Save reference frequency 
upon power outage 
1:Not save reference 
frequency upon power 
outage.   
Ten’s place of LED: 
0:Hold reference frequency 
at stop 
1:Clear reference 
frequency at stop 
Hundred’s place of LED: 

00 

○ 

0~11H 

Function

 

code 

Name 

Descriptions 

Unit 

Factory 

setting 

Modif 

Setting 

range 

0:UP/DN integral time 
valid 
1:UP/DN speed value 

A2.04 

Jog operating 
frequency 

0.10~50.00Hz 

0.01Hz 

5.00 

○ 

10~5000 

A2.05 

Interval of Jog 
operation 

0.0~100.0s 

0.1s 

0.0 

○ 

0~1000 

A2.06 

Skip frequency 1 

0.00~300.00Hz 

0.01Hz 

0.00 

× 

0~30000 

A2.07 

Range of skip 
frequency 1 

0.00~30.00Hz 

0.01Hz 

0.00 

× 

0~3000 

A2.08 

Skip frequency 2 

0.00~300.00Hz 

0.01Hz 

0.00 

× 

0~30000 

A2.09 

Range of skip 
frequency 

0.00~30.00Hz 

0.01Hz 

0.00 

× 

0~3000 

A2.10 

Skip frequency 3 

0.00~300.00Hz 

0.01Hz 

0.00 

× 

0~30000 

A2.11 

Range of skip 
frequency 3 

0.00~30.00Hz 

0.01Hz 

0.00 

× 

0~3000 

Group A3:Setting curve 

A3.00 

Reference 
frequency   
curve selection 

LED unit’s place:   
AI curve selection       
0: Curve 1 
1: Curve 2 
2: Curve 3 
3: Curve 4 

3330 

○ 

0~3333H 

A3.01 

Max reference of 
curve 1 

A3.03~110.00% 

0.01% 

100.00% 

○ 

0~11000 

A3.02 

Actual value   
Corresponding to 
the Max reference 
of curve 1 

Reference frequency:   
0.0~100.00%Fmax 
Torque: 0.0~300.00%Te 

0.01% 

100.00% 

○ 

0~10000 

A3.03 

Min reference of 
curve 1 

0.0%~A3.01 

0.01% 

0.00% 

○ 

0~11000 

A3.04 

Actual value   
Corresponding to 
the Min reference 
of curve 1 

The same as A3.02 

0.01% 

0.00% 

○ 

0~10000 

A3.05 

Max reference of 
curve 2 

A3.07~110.00% 

0.01% 

100.00% 

○ 

0~11000 

A3.06 

Actual value 
corresponding to 
the Max reference 
of curve 2 

The same as A3.02 

0.01% 

100.00% 

○ 

0~10000 

A3.07 

Min reference of 
curve 2 

0.0%~A3.05 

0.01% 

0.00% 

○ 

0~11000 

A3.08 

Actual value   
Corresponding to 
the Min reference 
of curve 2 

The same as A3.02 

0.01% 

0.00% 

○ 

0~10000 

A3.09 

Max reference of 
curve 3 

A3.11~110.00% 

0.01% 

100.00% 

○ 

0~11000 

A3.10 

Actual value   
Corresponding to 
the Max reference 
of curve 3 

The same as A3.02 

0.01% 

100.00% 

○ 

0~10000 

A3.11 

Min reference of 
curve 3 

0.0%~A3.09 

0.01% 

0.00% 

○ 

0~11000 

A3.12 

Actual value 
corresponding to 
the Min reference 
of curve 3 

The same as A3.02 

0.01% 

0.00% 

○ 

0~10000 

A3.13 

Max reference of 
curve 4 

A3.15~110.00% 

0.01% 

100.00% 

○ 

0~11000 

A3.14 

Actual value   
corresponding to 
the Max reference 
of curve 4 

The same as A3.02 

0.01% 

100.00% 

○ 

0~10000 

A3.15 

Reference of   
inflection point 2 
of curve 4 

A3.17~A3.13 

0.01% 

100.00% 

○ 

0~11000 

A3.16 

Actual value   
corresponding to 
the Min reference 
of inflection point 
2 of curve 4 

The same as A3.02 

0.01% 

100.00% 

○ 

0~10000 

A3.17 

Reference of 
inflection point 1 
of curve 4 

A3.19~A3.15 

0.01% 

0.00% 

○ 

0~11000 

A3.18 

Actual value 
corresponding to 
the Min reference 
of inflection point 
1 of curve 4 

The same as A3.02 

0.01% 

0.00% 

○ 

0~10000 

A3.19 

Min reference of 
curve 4 

0.0%~A3.17 

0.01% 

0.00% 

○ 

0~11000 

A3.20 

Actual value 
corresponding to 
the Min reference 
of curve 4 

The same as A3.02 

0.01% 

0.00% 

○ 

0~10000 

Group A4

Acc/Dec parameters 

A4.00 

Acc/Dec mode 

0: Linear Acc/Dec 
1: S Curve 

× 

0~1 

A4.01 

Acc time 2 

0.0~6000.0 

0.1 s 

20.0 s 

○ 

0~60000 

A4.02 

Dec time 2 

0.0~6000.0 

0.1 s 

20.0 s 

○ 

0~60000 

A4.03 

Acc time 3 

0.0~6000.0 

0.1 s 

20.0 s 

○ 

0~60000 

Function

 

code 

Name 

Descriptions 

Unit 

Factory 

setting 

Modif 

Setting 

range 

A4.04 

Dec time 3 

0.0~6000.0 

0.1 s 

20.0 s 

○ 

0~60000 

A4.05 

Acc time 4 

0.0~6000.0 

0.1 s 

20.0 s 

○ 

0~60000 

A4.06 

Dec time 4 

0.0~6000.0 

0.1 s 

20.0 s 

○ 

0~60000 

A4.07 

S curve 
acceleration 
starting time 

10.0%~50.0%(Acc time) 
A4.07+ A4.08≤90% 

0.1% 

20.0% 

○ 

100~500 

A4.08 

S curve 
acceleration ending 
time 

10.0%~70.0%(Acc time) 
A4.07+ A4.08≤90% 

0.1% 

20.0% 

○ 

100~800 

A4.09 

S curve 
deceleration 
starting time 

10.0%~50.0%(Dec time) 
A4.09+ A4.10≤90% 

0.1% 

20.0% 

○ 

100~500 

A4.10 

S curve 
deceleration 
ending time 

10.0%~70.0%(Dec time) 
A4.09+ A4.10≤90% 

0.1% 

20.0% 

○ 

100~800 

A4.11 

Quick start-stop 
selector 

0: Disable 
1: Quick start,normal stop 
2: Normal start,quick stop 
3: Quick start,quick stop 

× 

0~3 

A4.12 

Start ACR-P 

0.1~200.0 

0.1 

20.0 

○ 

1~2000 

A4.13 

Start ACR-I 

0.000~10.000s 

0.001 s 

0.200s 

○ 

0~10000 

A4.14 

Start AVR-P 

0.1~200.0 

0.1 

20.0 

○ 

1~2000 

A4.15 

Start AVR-I 

0.000~10.000s 

0.001 s 

0.200s 

○ 

0~10000 

A4.16 

Stop ACR-P 

0.1~200.0 

0.1 

20.0 

○ 

1~2000 

A4.17 

Stop ACR-I 

0.000~10.000s 

0.001 s 

0.200s 

○ 

0~10000 

A4.18 

Stop AVR-P 

0.1~200.0 

0.1 

20.0 

○ 

1~2000 

A4.19 

Stop AVR-I 

0.000~10.000s 

0.001 s 

0.200s 

○ 

0~10000 

A4.20 

Over 
Commtatation Stop 

0: disable 
1:enable 

× 

0~1 

A4.21 

ACC/DEC time 
coefficient 

0:ACC/DEC time × 1 
1: ACC/DEC time × 0.1 

× 

0~1 

A4.22 

ACC/DEC time 
1/2 switch freq. 

0.00~300.00Hz 
Select ACC/DEC time 2 
when output freq. is less 
than A4.22 

0.01Hz 

0.00Hz 

× 

0~30000 

A4.23~

A4.40 

Reserved 

Reserved 

○ 

0~65535 

Group A5

reserved 

Group A6

Control terminals parameters 

A6.00~

A6.03 

Multi-function 
terminal X1~X4 

0: No function1:Forward 
2: Reverse   
3: Forward jog operation 
4: Reverse jog operation 
5: 3-wire operation control 
6: External RESET signal 
input 
7: External fault signal 
input 
8: External interrupt signal 
input 
9: Drive operation prohibit 
10: External stop command 
11: DC injection braking 
command 
12: Coast to stop 
13: Frequency ramp up 
(UP) 
14: Frequency ramp down 
(DN) 
15: Switch to panel control 
16: Switch to terminal 
control 
17: Switch to 
communication control 
mode 
18: Main reference 
frequency via AI 
27: Preset frequency 1 
28: Preset frequency 2 
29: Preset frequency 3 
30: Preset frequency 4 
31: Acc/Dec time 1 
32: Acc/Dec time 2 
33: Multiple close-loop 
reference selection 1 
34: Multiple close-loop   
reference selection 2 
35: Multiple close-loop   
reference selection 3 
36: Multiple close-loop   
reference selection 4 
37: Forward prohibit 
38: Reverse prohibit 
39: Acc/Dec prohibit 
40: Process close-loop 
prohibit 
42: Main frequency switch 
to digital setting 
43: PLC pause 
44: PLC prohibit 
45: PLC stop memory clear   
46: Swing input 
47: Swing reset 

× 

0~54 
 