7-6 Setting Cyclic Communications Range
7 - 12
Builder
Chapter 7 Run Parameter Setting
M
M
M
E
E
E
M
M
M
O
O
O
♦
One hundred ranges can be set for cyclic communications.
♦
Shared memory and register setting ranges for cyclic communications
cannot overlap.
Example:
First range:
CW0 to CW9 and 1: MW0 to 1:MW9
Second range:
CW5 to CW14 and 1: MW10 to 1:MW19
In this case CW5 to CW9 are duplicated.
If two or more of the points in the memory are the same, an error occurs
after OK button is clicked.
♦
Even if the MP2500 register is a bit register, a bit number cannot be
selected. Execute cyclic communications from the 0 bit of the address by
using words.
♦
Select “Layout points” and “Start No.” without exceeding the allowable
range for the addresses of the register and the shared memory. This range
is selected by the last bit of the address.
♦
If “Layout points” and “Start No.” are selected, the addresses cannot be
edited, because the calculations for End No. are automatically done.
Blank if the settings for “Layout points” and “Start No.” are incorrect:
setting is blank, out of range, or the character string.
♦
Unable to select a high-speed protocol for the MP2500 register.