8-3 Shared Memory Batch Monitor
8
−
15
Builder
Chapter 8 Test
String input
1. Click the word memory address number to change, then press the [F4]
key.
2. The [String change] dialog box is displayed.
Number
Item Contents
1)
String
Sets the value of the text to input.
2)
Do not write
the 0 at the
end of string
Does not write 0 at the end of the string.
Example: If “ab” (H6261) is stored in CW0, the results of
writing “c” is as follows:
y
Without check
“H0063” (c) is stored to CW0.
y
Checked
“H6263” (cb) is stored to CW0.
3) Start
from
upper byte
Writes the upper byte as the starting point.
Example: The results of writing “a” to CW0 is as follows:
y
Without check
“H0061” is stored to CW0.
y
Checked
“H6100” is stored to CW0.
4)
String type
Selects the string type to input.
5) Read
current
value
Reads the current value.
3. Click the [Go] button after setting the necessary items.
1)
2)
3)
4)
5)