No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
S3-17
(322A) Secondary PI Feedback
Detection Selection
PI2 FB Det Sel
0: PI2 Enabled
1: Always
Selects when secondary PI controller low and high feedback
detection are active.
0: Secondary PI enabled
1: Always
Default: 0
Range: 0, 1
–
<1> Unit is determined by S3-04.
<2> Upper limit is S3-02, decimal placeholder is determined by S3-03.
u
S6: Protection
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
S6-01
(3236)
Emergency Override
Speed
E Override Speed
Sets the speed command used in emergency override mode
when S6-02 = 0.
Default: 0.00 Hz
Min.: 0.00
Max.: 240.00
–
S6-02
(3237)
Emergency Override
Reference Selection
E OverrideRefSel
0: Use S6-01 Ref
1: Use Freq Ref
Selects the emergency override speed source.
0: Use S6-01 Reference
1: Use Frequency Reference
Default: 0
Range: 0, 1
–
S6-07
(323C)
Output Phase Loss
Level for Dynamic
Noise Control
DNC Outp Ph Loss
Reduces the output phase loss level when Dynamic Noise
Control is active.
Default: 100.0%
Min.: 10.0
Max.: 100.0
–
B.13 S: Special Application
324
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Содержание iQpump1000
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 12: ...This Page Intentionally Blank 12 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 353: ...This Page Intentionally Blank YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide 353...