Step
7
No.
Value
Description
Reference
Comments
b5-03
3.0 sec.
PI Integral Time
Decrease integral time to make iQpump more responsive.
Caution:
can cause instability if
value is too low.
b5-12
2
(Fault)
PI Feedback Ref-
erence Missing
Detection Selec-
tion
Select what to do when the feedback device (transducer) fails or gets disconnected.
0: Disabled, continue running no message is displayed
1: Alarm, show warning on the keypad when the feedback device fails or is discon-
nected
2: Fault, stop pump system when the feedback fails or is disconnected
NOTE:
Disable parameter b5-12
if no transducer is installed.
C1-01
20.0 sec.
See Note
Acceleration Time
1
Time it takes to accelerate the pump motor from zero to maximum speed.
NOTE:
Factory default with Thrust Mode enabled is 12.0 sec, 20.0 sec when dis-
abled.
Adjusted depending on system
performance
C1-02
10.0 sec.
See Note
Deceleration
Time 1
Time it takes to decelerate the pump motor from maximum speed to zero.
NOTE:
Factory default with Thrust Mode enabled is 5.0 sec, 10.0 sec when dis-
abled.
L5-01
5
Number of Re-
start Attempts
Determines the number of times iQpump will perform an automatic restart on the
faults listed in the comments column.
iQpump System Protection Faults that can be setup to restart are Low Level Feed-
back,
High Level Feedback, Transducer Loss, Not Maintaining Setpoint, Loss of Prime,
Pump Over Cycle. Refer to parameters P4-07 and P4-08. The number of restart at-
tempts is set by L5-01.
Overcurrent
Ground Fault
Output Phase Loss
Input Phase Loss
iQpump Overload
Motor Overload
Overtorque
DC Bus Fuse Blown
DC Bus Undervoltage
DC Bus Overvoltage
Overheat
L5-03
20 sec.
Maximum Restart
Time After Fault
If the restart fails (or is not attempted due to a continuing fault condition) iQpump
waits the Maximum Restart Time After Fault, before attempting another restart.
P1-06
40.0 Hz
Minimum Pump
Frequency
Minimum speed (Hz) the pump motor has to operate at.
Example: Base pump motor speed is 3600 RPM, minimum speed is 2400 RPM. Set
minimum pump frequency to 40.0 Hz. (2400 ÷ 3600 x 60 Hz = 40 Hz)
P1-06 should be set to the level
where the pump can produce the
minimum pressure even at zero
flow.
P2-03
5 sec.
Sleep Delay Time
Time it takes before the pump system goes to sleep when the selected signal level
(P2-01) falls below the specified sleep level (P2-02)
Adjust according to system
requirements.
P4-12
30.0 Hz
Thrust Bearing
Frequency
Sets the frequency reference used when the thrust bearing function is active. A
value of 0 disables this function.
Primarily used for submersible
pumps. Program P4-12 = 0.0 Hz
to disable function when iQpump is
used with a centrifugal pump.
P4-17
0.2 Min
Utility Start Delay
When utility power is restored and P4-10 is enabled (1), iQpump waits the time
specified in P4-11 before auto operation becomes active.
Note: Only active when P4-10 is
enabled (1) and operation
(start/stop) is from the
digital operator.
iQpump Factory Defaults Overview
(adjust certain settings specific to the application)
P1-03 = 200.0 PSI Feedback Scaling
P1-02 Feedback Unit
0: Inch of Water
8: Bar
1: PSI
9: Pascal
2: GPM
10: Degrees Celsius
3: Degrees Fahrenheit
11: Meter
4: CFM
12: Feet
5: CMH
13: Liters per Minute
6: Liters / Hr
14: cm per Minute
7: Liters/Sec
15: Inch Hg
25: No Unit
Feedback
Maximum
SYSTEM FEEDBACK UNIT /
FEEDBACK DEVICE SCALING
1
START / DRAW DOWN LEVEL
Start Pump System
Start
Delay
200
PSI
Start / Draw Down Level (P1-04)
(Example 100.0 PSI)
System Setpoint
(Example 150.0 PSI)
Feedback Signal from pressure
transducer (4 – 20 mA)
0
Time
Pressure
Start Level Delay (P1-05)
(Example 5.0 sec.)
System Units (P1-02)
(Example PSI)
Feedback Scaling (P1-03)
(Example 200.0 PSI)
WAIT
2
SYSTEM STARTS WHEN
PRESSURE SIGNAL FALLS
BELOW 100 PSI
Example: Absolute Level (Positive Start Level)
Example: Delta Level (Negative Start Level)
150
Start Pump System
Start
Delay
Start / Draw Down Level (P1-04)
(Example -50.0 PSI, (150.0 – 50.0)
System Setpoint
(Example 150.0 PSI)
Feedback Signal from pressure
transducer (4 – 20 mA)
Time
Pressure
Start Level Delay (P1-05)
(Example 5.0 sec.)
System Units (P1-02)
(Example PSI)
Feedback Scaling (P1-03)
(Example 200.0 PSI)
WAIT
SYSTEM STARTS WHEN
PRESSURE SIGNAL FALLS
BELOW 100 PSI
-50.0 PSI
150
200
PSI
START / DRAW DOWN LEVEL
8
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Содержание iQpump1000
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 12: ...This Page Intentionally Blank 12 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 353: ...This Page Intentionally Blank YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide 353...
Страница 355: ......