No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U1-83
(0B9E) Flow Rate
Flow Rate
Displays the flow rate based on the pulse input frequency or the
analog voltage (flow rate input) and parameters P6-01 and
P6-04.
A 2-second first order filter will be applied to this monitor.
Full scale: P6-01
setting
dep. on
P6-04
U1-84
(0B9F)
Accumulation Level -
Millions
Volume * 1000000
Displays the recorded volume from the flow meter (pulse input
or analog voltage).
Total volume is calculated as follows:
Total Volume = (U1-84 * 1000000) + (U1-85 * 1000) + U1-86
+ U1-87
No signal output
available
dep. on
P6-16
U1-85
(0BA0)
Accumulation Level -
Thousands
Volume * 1000
U1-86
(0BA1)
Accumulation Level -
Ones
Volume * 1
U1-87
(0BA2)
Accumulation Level -
Decimal
Volume * 0.0001
U1-90
(0BA5) Pump Setpoint
Pump Setpoint
Displays the PID Setpoint.
No signal output
available
dep. on
P1-02
U1-91
(0BA6) Pump Feedback
Pump Feedback
Displays the PID Feedback.
No signal output
available
dep. on
P1-02
U1-92
(0BA7) Pump Status
Pump Status
Displays Pump Running Status.
U1 - 92=
00000000
Drive
Pump 2
Pump 3
Pump 4
Pump 5
Pump 6
Not used
Not used
1
1
1
1
1
1
0
0
No signal output
available
–
U1-93
(0BA8)
Total Setpoint
Compensation
Total SP Comp.
Displays the total absolute Setpoint Compensation.
No signal output
available
dep. on
P1-02
U1-94
(0BA9) Motor Speed
Motor Speed
Displays the absolute value of the output frequency (U1-02)
converted to RPM.
No signal output
available
1 RPM
U1-97
(0BAC) Water Level
Water Level
Displays the amount of water above the water level sensor.
Full scale:
10 V = Q4-02
0.1 ft.
U1-98
(0BAD) Suction Pressure
Suction Pressure
Displays the amount of suction pressure.
Full scale:
10 V = Q5-02
0.1 PSI
or ”Hg
U1-99
(0BAE) Anti-No-Flow Timer
ANF Timer
The Anti-No-Flow reduces the output frequency when this
value reaches the P2-24 setting.
No signal output
available
0.1 s
<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<4> The display resolution depends on the ND selection. This value has two decimal places (0.01 kW) if the drive is set for a maximum applicable
u
U2: Fault Trace
No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U2-01
(0080)
Current Fault
Current Fault
Displays the current fault.
No signal output
available
–
U2-02
(0081)
Previous Fault
Last Fault
Displays the previous fault.
No signal output
available
–
U2-03
(0082)
Frequency Reference at
Previous Fault
Frequency Ref
Displays the frequency reference at the previous fault.
No signal output
available
0.01 Hz
B.15 U: Monitors
328
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Содержание iQpump1000
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 12: ...This Page Intentionally Blank 12 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 353: ...This Page Intentionally Blank YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide 353...
Страница 355: ......