HOA Keypad Display
Fault Name
Err
EEPROM Write Error
Data cannot be written to the EEPROM
Cause
Possible Solution
Noise has corrupted data while writing to
the EEPROM
• Press “ENTER” on the digital operator.
• Correct the parameter setting.
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Hardware problem
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
HOA Keypad Display
Fault Name
FAn
Internal Fan Fault
Fan or magnetic contactor failure
Cause
Possible Solution
Internal cooling fan has malfunctioned
• Cycle power to the drive.
• Check for fan operation.
• Verify the cumulative operation time of the fan with monitor U4-03, and verify the cumulative operation
time of the fan maintenance timer with U4-04.
• If the cooling fan has exceeded its expected performance life or is damaged in any other way, follow the
replacement instructions in the
Fault detected in the internal cooling fan or
magnetic contactor to the power supply.
• Cycle power to the drive.
• If the fault continues to occur, replace the power board/gate drive board or the entire drive.
• Contact Yaskawa or a Yaskawa representative for instructions on replacing the power board/gate drive
board.
HOA Keypad Display
Fault Name
FDBKL Wire Break
PID Feedback Loss
The analog input programmed for PID feedback has risen above 21 mA or fallen below 3 mA.
Cause
Possible Solution
The analog input programmed for PID
feedback loss has risen above 21 mA or
fallen below 3 mA. This is effective only
when b5-12 Feedback Loss 4 to 20 mA
Detection Selection is set to 2 (fault).
• Confirm that the PID feedback source is installed and working properly.
• Drive response to this condition is controlled by b5-12, Feedback Loss 4 to 20 mA Detection Selection
and b5-13, Feedback Loss Go To Frequency.
• Auto-restart of this fault is controlled by L5-42, Feedback Loss Fault Retry Selection.
HOA Keypad Display
Fault Name
GF
Ground Fault
• A current short to ground exceeded 50% of rated current on the output side of the drive.
• Setting L8-09 to 1 enables ground fault detection.
Cause
Possible Solution
Motor insulation is damaged
• Check the insulation resistance of the motor.
• Replace the motor.
A damaged motor cable is creating a short
circuit
• Check the motor cable.
• Remove the short circuit and reapply power to the drive
• Check the resistance between the cable and the ground terminal .
• Replace the cable.
Excessive leakage current at the drive
output
• Reduce the carrier frequency.
• Reduce the amount of stray capacitance.
The drive started to run during a current
offset fault or while coasting to a stop
• Set b3-01 to 1 to enable Speed Search at Start.
• Perform Speed Search 1 or 2 (H1-
oo
= 61 or 62) via one of the external terminals.
Hardware problem
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
HOA Keypad Display
Fault Name
HFB
High Feedback
The feedback signal is too high.
5.2 Fault Detection
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
179
5
Troubleshooting
Содержание iQpump1000
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 12: ...This Page Intentionally Blank 12 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 353: ...This Page Intentionally Blank YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide 353...
Страница 355: ......