No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
P9-51
(0E26)
Low Water Level/
Suction Pressure Turn-
Off Method
Low WL Turn-Off
0: Disabled
1: Enabled
Determines the MEMOBUS multiplex response to Water Level
or Suction Pressure.
0: Disabled
• Water level does not have an effect on Idle or Lag drives
• Water level will not cause alternation
1: Enabled
• A drive is considered offline when the Water Level/Suction
Pressure is below the wake-up level set in Q4-06/Q5-06.
• A Lag drive is removed when the Water Level/Suction
Pressure is below the wake-up level set in Q4-06/Q5-06.
• A Lead drive is alternated if in Level Control/Suction
Pressure while the Water Level is below the septoint set in
Q4-03/Q5-03.
Default: 0
Range: 0, 1
–
P9-60
(0E2F)
Geothermal
Temperature Source
Geo Temp Source
0: Analog only
1: Ana->Net, No Alrm
2: Ana->Net, Alarm
3: Network only
0: Analog only
1: Ana->Net, No Alrm
2: Ana->Net, Alarm
3: Network only
Default: 0
Range: 0 to 3
–
P9-99
(0E56)
Network Compatibility
Selection
Network Comp Sel
0: A-Ver: 30034
1: B-Ver: 30035/36
2: iQ SmartNetwork
Determines the communication compatibility for the iQPump
MEMOBUS network.
0: A-Ver: 30034
1: B-Ver: 30035/36
2: iQ SmartNetwork
Default: 2
Range: 0 to 2
–
<1> Unit text is set by P1-18, Prime Loss Detection Method.
B.11 P: Pump Parameters
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
315
B
Parameter List