Step
1
iQpump Model
Identification and Mounting
To make sure you received the correct model, it is
essential to verify the iQpump nameplate with your order
and make sure the iQpump has the correct rating so it can
be used with your motor. Please check the nameplate
information as shown in the example below.
Check that the available power will meet the
input
power
requirements.
Ensure that the
output power
from the iQpump is
compatible with the motor requirements.
Mounting the iQpump
In the case of systems with more than one iQpump, follow
the above procedure for each iQpump and motor.
The mounting of the iQpump is extremely important
regarding environment and accessibility. Depending on your
system, there are various models available and the mounting
dimensions (footprint) may be different. Because the
mounting procedure is fairly extensive, it is beyond the scope
of this document; Refer to the iQpump1000
Quick Start Guide (Document No. TOEPYAIP1W01)
received with the iQpump,
Section 2.2 Mechanical
Installation
. Match the model that you received and follow
the procedure described in the manual to ensure a safe and
functional installation. In cases where the system has more
than one iQpump, refer to the proper clearances required for
adequate ventilation. Please pay particular attention to:
The clearances to be maintained around the enclosure
for adequate ventilation.
The environmental specifications such as avoiding
excessive dampness, extreme temperatures, chemical
exposure, corrosive areas, etc. to avoid damage to the
equipment and to maintain safety.
Removing and Attaching the Terminal Cover
Improper removal of the iQpump terminal cover as well as
front cover can cause extensive damage to the iQpump. To
avoid damage to these items, please pay particular attention
Open Chassis
NEMA 1
Drive Model
Number
Input Power
Rating
Output
Power
Rating
Serial
Number
UL File
Number
Drive Spec Number
Weight
Software
Version
Normal
Duty Amps
CIMR-PW2A0021FAA
CIMR-PW2A0021FAA
CC :
8000
6W3050 - 2 - 100
J0073D207410100
to the
iQpump1000 Quick Start Guide TOEPYAIP1W01
Section 3.5 Removing and Attaching the Terminal Cover.
Connect Motor and
Line Power
Step
2
WARNING DO NOT CONNECT ANY OF THE
FOLLOWING TERMINALS TO EARTH GROUND
B1
B2
-
+1
+2
+3
NOT USED
Fig.1 & 2
below show the electrical connections for the input
power and motor terminals for various iQpump models.
Select
the proper diagram for the model you are installing
(see Step
1).
WITH POWER OFF
make the appropriate connections.
Make sure to follow good wiring practices and all
applicable codes. Ensure that the equipment is grounded
properly as shown in fig. 1
DANGER; LETHAL VOLTAGES ARE PRESENT - Before
applying power to the iQpump, ensure that the terminal
cover is fastened and all wiring connections are secure.
After the power has been turned OFF, wait at least five
minutes until the charge indicator extinguishes
completely before touching any wiring, circuit boards or
components.
!
Make sure the iQpump has been properly sized for single phase input
power. For best performance, the drive input supply voltage must be
equal to or greater than the motor rated voltage.
3Ø Induction
motor
Connect
frame to
ground
Input
Protection
(Fuse or Circuit
Breaker)
To change direction of motor
rotation swap any
two
of the
three
motor leads.
Fig. 2 Input Power and Output Motor Electrical Connections for
Models: 2_0110 & Larger and 4_0058 & Larger
(R/L1)
(S/L2)
(T/L3)
(U/T1)
(V/T2)
(W/T3)
Connect to
chassis
ground
Use L1, L2, L3 for
3Ø Input Power
L1 L2 L3
Use L1, L2 for
1Ø Input Power
*
BUS TERMINALS:
DO NOT CONNECT TO GROUND
Use L1, L2, L3 for
3Ø Input Power
To change
direction of
motor rotation
swap any
two
of the
three
motor leads.
Fig. 1 Input Power and Output Motor Electrical Connections for
Models:
2_0004
-
2_0056,
4_0002
-
4_0044 and 5_0003 - 50011
Use L1, L2 for
1Ø Input Power
3Ø Induction
motor
Connect
frame to
ground
Input
Protection
(Fuse or Circuit
Breaker)
L1 L2 L3
(R/L1)
(S/L2)
(T/L3)
(U/T1)
(V/T2)
(W/T3)
Connect to
chassis ground
*
DC Bus terminals
location varies by
model.
*
Step
3
Real-time
Clock Setup
This step shows how to setup the
iQpump real-time clock for first
use.
Note:
If clock is not set the drive
can still be programmed and
operated, but ALM light will flash
every 30s and showing
Clock
Not Set
message.
Power up the drive and set the
real-time Clock. The real-time
Clock setup screen will appear at
first power up.
Press to set the clock.
Note:
After the real-time clock is
set the real-time clock setup
screen will not show again unless
parameter o4-17 is set to “Set”.
Real-time Clock Setup Screen
Use to move cursor to
The left and to move
cursor to the right
use to adjust.
When date and time are set
press to save.
Note:
Do NOT adjust sec per
month.
Example:
Jun 12
th
2012, 7:35am
4
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Содержание iQpump1000
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 12: ...This Page Intentionally Blank 12 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 353: ...This Page Intentionally Blank YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide 353...
Страница 355: ......