There is loose wiring in the drive input
power terminals
• Ensure the terminals are tightened properly.
• Apply the tightening torque as specified in this manual.
Refer to Wire Gauges and Tightening Torque
There is excessive fluctuation in the drive
input power voltage
• Check the voltage from the drive input power.
• Review the possible solutions for stabilizing the drive input power.
There is poor balance between voltage
phases
Stabilize drive input power or disable phase loss detection.
The main circuit capacitors are worn out
• Check the maintenance time for the capacitors (U4-05).
• Replace the capacitor if U4-05 is greater than 90%. For instructions on replacing the capacitor, contact
Yaskawa or a Yaskawa representative.
Check for problems with the drive input power. If drive input power appears normal but the alarm continues
to occur, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or a Yaskawa representative.
HOA Keypad Display
Fault Name
PoC
Pump Over Cycle
Cause
Possible Solution
The pump has exceeded the number of
cycles set in P2-10 in the time set in P2-11
and P2-12 is set to 2 (fault).
• Set the Pump Over Cycle fault characteristics in P2-10 and P2-11.
• Drive response to this condition is controlled by P2-12, Over Cycling Mode.
• Auto-restart of this fault is controlled by L5-52, Pump Over Cycle Fault Retry Selection.
• Set the Pump Over Cycle automatic setpoint compensation in P2-12, Over Cycling Mode, P2-13, Setpoint
Compensation, and P2-14, Maximum Setpoint Compensation.
HOA Keypad Display
Fault Name
rF
Braking Resistor Fault
The resistance of the braking resistor is too low.
Cause
Possible Solution
The proper braking resistor option has not
been installed
Select a braking resistor option that it fits the drive braking transistor specification.
A regenerative converter, regenerative unit,
or braking unit is being used
Set L8-55 to 0 to disable the braking transistor protection selection.
HOA Keypad Display
Fault Name
rH
Braking Resistor Overheat
Braking resistor protection was triggered.
Fault detection is enabled when L8-01 = 1 (disabled as a default).
Cause
Possible Solution
Deceleration time is too short and excessive
regenerative energy is flowing back into the
drive
• Check the load, deceleration time, and speed.
• Reduce the load inertia.
• Increase the deceleration times (C1-01 to C1-04).
• Replace the dynamic braking option with a larger device that can handle the power that is discharged.
The duty cycle is too high
Check the duty cycle. Maximum of 3% duty cycle is available when L8-01 = 1.
Excessive braking inertia
Recalculate braking load and braking power. Reduce the braking load by adjusting braking resistor settings.
The braking operation duty cycle is too
high
Check the braking operation duty cycle. Braking resistor protection for ERF-type braking resistors
(L8-01 = 1) allows a braking duty cycle of maximum 3%.
The proper braking resistor has not been
installed
• Check the specifications and conditions for the braking resistor device.
• Select the optimal braking resistor.
Note:
The magnitude of the braking load trips the braking resistor overheat alarm, NOT the surface temperature. Using the braking resistor more
frequently than its rating permits will trip the alarm even when the braking resistor surface is not very hot.
HOA Keypad Display
Fault Name
rr
Dynamic Braking Transistor
The built-in dynamic braking transistor failed.
Cause
Possible Solution
The braking transistor is damaged
• Cycle power to the drive and check for reoccurrence of the fault.
• Replace either the control board or the entire drive. For instructions on replacing the control board, contact
Yaskawa or a Yaskawa representative.
The control circuit is damaged
5.2 Fault Detection
188
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide