u
Three-Phase 200 V Class Drive Models 2A0250 to 2A0415
Table A.3 Power Ratings Continued (Three-Phase 200 V Class)
Item
Specification
Drive Models
2A0250
2A0312
2A0360
2A0415
Maximum Applicable Motor Capacity (HP)
ND Rating
100
125
150
175
Input
Input Current (A)
ND Rating
271
324
394
471
Rated Voltage
Rated Frequency
Three-phase 200 to 240 Vac 50/60 Hz/270 to 340 Vdc
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Input Power (kVA)
ND Rating
124
148
180
215
Output
Rated Output Capacity (kVA)
ND Rating
95
119
137
158
Rated Output Current (A)
ND Rating
250
312
360
415
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User-adjustable between 1 and 10 kHz
Maximum Output Voltage (V)
Three-phase 200 to 240 V (proportional to input voltage)
Maximum Output Frequency (Hz)
400 Hz (user-set)
connections, and power supply impedance.
<3> DC is not available for UL/CE standards.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency default setting is Swing PWM 1 (C6-02 = 7). C6-02 settings 1, 7, 8, 9, and A do not require current derating. All other settings
raise the carrier frequency and require current derating.
A.1 Power Ratings
236
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide