No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H3-17
(02F1) Terminal A2 Offset
Term A2 Offset
Adds an offset when the analog signal to terminal A2 is at 0 V.
Default: 0
Min.: -500
Max.: 500
–
H3-18
(02F2) Terminal A3 Offset
Term A3 Offset
Adds an offset when the analog signal to terminal A3 is at 0 V.
Default: 0
Min.: -500
Max.: 500
–
H3 Multi-Function Analog Input Settings
H3-
oo
Setting
Function
LCD Display
Description
Page
0
Frequency bias
Freq Ref Bias
10 V = E1-04 (maximum output frequency)
–
1
Frequency gain
Freq Ref Gain
0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting
of -100 to 0%.
–
2
Auxiliary frequency
reference 1
Aux Reference1
10 V = E1-04 (maximum output frequency)
–
3
Auxiliary frequency
reference 2
Aux Reference2
10 V = E1-04 (maximum output frequency)
–
4
Output voltage bias
Voltage Bias
V/f
V/f
10 V = E1-05 (motor rated voltage)
–
5
Accel/decel time gain
Acc/Dec Change
10 V = 100%
–
6
DC Injection Braking
current
DC Brake Current
10 V = Drive rated current
–
7
Overtorque/
undertorque
detection level
Torque Det Level
10 V = Drive rated current (V/f)
–
8
Stall Prevention level
during run
Stall Prev Level
V/f
V/f
10 V = Drive rated current
–
9
Output frequency lower
limit level
Ref Lower Limit
10 V = E1-04 (maximum output frequency)
–
B
PID feedback
PID Feedback1
10 V = 100%
–
C
PID setpoint
PID Set Point
10 V = 100%
–
D
Frequency bias
Freq Ref Bias 2
10 V = E1-04 (maximum output frequency)
–
E
Motor Temperature
(PTC Input)
E Motor PTC
10 V = 100%
Note:
A 12 k
Ω
resistor must be connected between terminals A1, A2, or
A3 and V+ for PTC functionality.
–
F
Through mode
Not Used
Select this setting when using the terminal in a pass-through mode. The terminal
does not trigger a drive function but can be used as digital input for the controller
the drive is connected to.
–
10
Forward torque limit
Fwd Torque Limit
OLV
OLV
OLV
OLV
10 V = Motor rated torque
–
11
Reverse torque limit
Rev Torque Limit
OLV
OLV
OLV
OLV
10 V = Motor rated torque
–
12
Regenerative torque
limit
Regen Torq Limit
OLV
OLV
OLV
OLV
10 V = Motor rated torque
–
15
General torque limit
Torque Limit
OLV
OLV
OLV
OLV
10 V = Motor rated torque
–
16
Differential PID
feedback
PID Feedback 2
10 V = 100%
–
1F
Through mode
Not Used
Set this value when using the terminal in the pass-through mode.
–
20
HAND Frequency
Reference
Hand Freq. Ref.
Full scale: Max. frequency (E1-04)
–
21
Geothermal
Temperature
Geothermal Temp
Full scale: Q2-02 = 10 V (or 20 mA), Q2-01 = 0 V (or 4 mA)
This input is internally limited to -110.0
°
F to +320.0
°
F after gain and bias.
–
22
Flow Meter
Flow Meter
Full scale: P6-01
–
B.7 H Parameters: Multi-Function Terminals
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
285
B
Parameter List
Содержание iQpump1000
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 12: ...This Page Intentionally Blank 12 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 353: ...This Page Intentionally Blank YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide 353...
Страница 355: ......