WPC 1000 User Manual
1125100
Installation
2-33
To set the Micro-inch time, refer to Setting Micro-Inch, page 3-26.
Disabling Top-stop in Inch
By default, Inch mode is set so that the ram top-stops whenever the Run/Inch palm buttons on
the Operator Station are pressed and held continuously (see Top-stop in Inch, page 4-8). You
can disable this default setting, allowing the ram to continue cycling in Inch mode as long as
the Run/Inch buttons are depressed. To do so, connect pin #156 on terminal block TB 705 on
the WPC 1000 Display board to ground (pin #155). See Table 2-20, page 2-71.
Figure 2-16. WPC 1000 Display Board: Location of Important Components
Table 2-7. Micro-inch Wiring Connections
Display Board
TB705
Pin #
Signal
157
Micro-inch input
155
Ground
TB701
TB702
J707
133
134
TB708
1
157
156
155
TB705
J706
149
148
147
146
145
144
143
142
141
1
1
1
1
Micro-inch key switch
wiring connector
Mode Select key switch
wiring connector
Stroke Select key switch
wiring connector
Mute lamp wiring connector
Reset/Select button and
Settings key switch
wiring connector
Ribbon cable connector
(to WPC 1000 Control
board)
Содержание WPC 1000
Страница 17: ...1125100 WPC 1000 User Manual xii Table of Contents ...
Страница 69: ...1125100 WPC 1000 User Manual 2 42 Installation Figure 2 22 One hand Control Switch Mounting Dimensions ...
Страница 99: ...1125100 WPC 1000 User Manual 2 72 Installation ...
Страница 207: ...1125100 WPC 1000 User Manual A 18 Extracts from OSHA and ANSI ...
Страница 217: ...1125100 WPC 1000 User Manual G 6 Glossary ...
Страница 223: ......
Страница 224: ......
Страница 225: ......
Страница 226: ......
Страница 227: ......
Страница 228: ......
Страница 229: ......
Страница 230: ......
Страница 231: ......
Страница 232: ......
Страница 233: ......
Страница 234: ......
Страница 235: ......