Diesel Gen-set Operation Instructions
37
6.4 Owning to the fact that temperature of exhaust pipe is high, in order to prevent
burns and prevent rising of temperature in equipment room caused by radiant heat,
heat insulation treatment shall be carried out. And, heat insulation materials shall be
wrapped with glass fiber or aluminum silicate effective for heat insulation and noise
reduction. In addition, exhaust terminal and exposed part of exhaust pipe shall be kept
away from woods or other flammable substances.
6.5 Exhaust terminal shall be able to avoid dropping of rain water. The exhaust pipe
can be projected horizontally and chamfered at end to an angle of 30°~45°. In order
to prevent rain water and condensed fluid flows backward to the Gen-set. The exhaust
pipe placed horizontally shall be titled to some angle, low end of it shall be kept away
from engine, silencer and any section of the pipe where condensed liquid exists (e.g.
vertical turn of exhaust pipe) shall be equipped with outlet.
6.6 Position of exhaust outlet shall be designed as per following principles:
1) Keep away from air intake;
2) Reduce noise impacts on environment;
3) Avoid dust generated in exhausting from accumulating on adjacent buildings.
7. Fuel supply system
Daily-use fuel tank and fuel pipelines shall be provided to this series of Gen-set
according to specific circumstances to supply fuel to the Gen-set.
7.1 Daily-use fuel tank
1) If using F series 10~50kW Gen-set as emergency power, it could using without
daily-use fuel tank. If the ‘B’ or ‘F’ series Gen-sets are used as daily power source,
you’d better select a daily-use fuel tank no less than 300L with proper capacity
meeting 24h continuous operation of the Gen-set under rated load.
2) The daily-used fuel tank shall be installed at a place which it is convenient for
refueling and not far away from the Gen-set. Except refilling oil to daily-use fuel tank