Diesel Gen-set Operation Instructions
16
procedures shall be followed:
Let the Gen-set to operate without load and check if its speed is correct or not;
Turn stability knob to the end clockwise and then turn it counterclockwise slowly
until voltage of alternator starts to fluctuate.
Note: correct setting will be completed just by slightly turning clockwise from
this position (namely, at this point, voltage of alternator is stable, but it is also
very close to unstable zone).
III. Control panel
Control panel is “brain” of the Gen-set as it not only enables starting, stopping, data
measurement, data display and fault protection of engine, but also enables electricity
measurement, electricity display and electricity protection, etc. of alternator. The
control panel of DSE6020 module or DSE7320 module can be provided with
mechanically governing or electronically governing diesel engine. Structure of the
control panel of DSE6020 module is as shown in Figure 3-8.
DSE6020 module
Power switch
Door lock
Emergency stop button
Air switch