Diesel Gen-set Operation Instructions
43
Chapter 7 Commissioning of the Gen-set
Carry out commissioning as per following methods after the Gen-set is installed:
I. Inspections before commissioning
1. Areas at around Gen-set shall be cleaned up and unsafe objects shall be moved
away, in order to prevent operation from being influenced or danger from being
caused and ensure that intake/exhaust duct for ventilation of equipment room is not
blocked;
2. Before inspection, check if key switch of control panel is “OFF” and emergency
stop switch is “ON”;
3. Check all electric circuits to see if wiring harness is damaged or leaks electricity or
not. If any, replace the wire; and, check if the connection is loose or damaged or not.
If any, tighten or replace it.
4. Check reliability of fasteners and throttle control system, confirm if various
operating mechanisms are flexible, portable and reliable and check pre-tensioning of
charger belt and fan belt;
5. Check if there is large amount of dust accumulating on control panel and Gen-set.
If any, clean it in order to prevent electric shock or reduction of cooling performance
of the Gen-set caused by these dust and impurities.
6. Check if electrodes of battery are corroded or not. If any, clean it. Check voltage of
battery, if it is less than 9V and does not meet starting requirements, charge the
battery.
Warning: do not place wrench, iron pipe or conductors on battery because this is
easy to cause short connection of positive and negative electrode of battery and
accidents.