8.4 Followings shall be paid attention to during storage of battery: it shall be kept in a
dry, clean and well-ventilated room in which temperature is 5~25 ; be kept away
℃
from direct sunlight, heat source, any liquid and hazardous substances; do not be
placed upside down or on the side; and prevent from being impacted or weighted.
After long period of service, the battery itself may discharge slowly, or even scrap.
Therefore, in order to ensure that the battery is always in good operating state,
recharge it at regular intervals.
Suggested charging interval is as follows:
Recharge once every 6 months when storage temperature is less than or equal to
20 ;
℃
Recharge once every 3 months when storage temperature is 20~30 ;
℃