Diesel Gen-set Operation Instructions
11
3.1 AS440
Figure 3-4 AS440 Structure diagram
1) Generally, terminal 8 and Z2 are short-connected. However, if the alternator is
equipped with auxiliary winding, they shall be disconnected and connected to
auxiliary winding;
2) As shown in Figure 3-5, terminal 7 and 8 are connected to main stator (armature)
of alternator and terminal F1 and F2 are connected to exciter stator (magnetic field);
Stability selection
Jumper
Jumper
Frequency selection
LED indicator light