Parameterization
SRW 01 | 5-11
5
P208 – Check Back Type
Adjustable
Range:
0 = Motor Current
1 = Digital Input Ix
2 = Simulation
Factory
Setting:
0
Proprieties:
Sys, CFG
Description:
Define the check back of the switch on/off control of the motor.
NOTE!
Parameter P208 configured for simulation (P208 = 2) does not monitor the switch On/Off control of the
motor. Therefore, it must be used only for testing.
If configured for digital input, P208 = 1, it must be verified what operation mode (P202) and what digital
input for that operation mode has the Check Back function. If adjusted for motor current, P208 = 0, the
digital input preconfigured for the Check Back function becomes free for the user, and can be used to
cause an external fault, for instance (refer to the
Item 5.7.2 External Fault on page 5-33
).
P209 – Execution Time
Adjustable
Range:
0.1 to 99.0 s
Factory
Setting:
0.5 s
Proprieties:
Sys, CFG
Description:
It defines the maximum waiting time of the check back signal to assure the setting of the on and off controls.
If the Control Unit identifies an on control and does not receive the check back signal in the time defined on
P209, an error will be generated and the control unit will send out a signal through the status led and message
“E0078” on the HMI.
If the Control Unit identifies an off control and keeps receiving the check back signal in the time defined on P209,
an error will be generated and the control unit will send out a signal through the status led and message “E0079”
on the HMI.