![background image](http://html1.mh-extra.com/html/weg/srw-01/srw-01_user-manual_950804116.webp)
Monitoring
6-8 | SRW 01
6
P031 – L2 Phase True RMS Current
Adjustable
Range:
0.0 to 6553.5 A
Padrão:
-
Proprieties:
RO
Description:
It informs the motor L2 phase True RMS current value.
P032 – L3 Phase True RMS Current
Adjustable
Range:
0.0 to 6553.5 A
Factory
Setting:
-
Proprieties:
RO
Description:
It informs the motor L3 phase True RMS current value.
P033 – Line Voltage L1-L2
Adjustable
Range:
0 to 1000 V
Factory
Setting:
-
Proprieties:
RO
Description:
It indicates the True RMS voltage between phases L1 and L2.
P034 – Line Voltage L2-L3
Adjustable
Range:
0 to 1000 V
Factory
Setting:
-
Proprieties:
RO
Description:
It indicates the True RMS voltage between phases L2 and L3.
P035 – Line Voltage L3-L1
Adjustable
Range:
0 to 1000 V
Factory
Setting:
-
Proprieties:
RO
Description:
It indicates the True RMS voltage between phases L3 and L1.
P036 – Earth Leakage Percentage Current
Adjustable
Range:
0 to 3334 %
Factory
Setting:
-
Proprieties:
RO
Description:
It informs the percentage of earth leakage current in relation to the current level set on parameter P632, as long
as the earth leakage protection is abled (P631 = 1).
Содержание SRW 01
Страница 1: ...User s Manual Smart Relay SRW 01 Ethernet Motors Automation Energy Transmission Distribution Coatings...
Страница 2: ......
Страница 8: ...Contents...
Страница 108: ...Parameterization 5 62 SRW 01 5...
Страница 128: ...Monitoring 6 20 SRW 01 6...