Monitoring
SRW 01 | 6-5
6
P008 – Power Factor
Adjustable
Range:
0.00 to 1.00
Factory
Setting:
-
Proprieties:
RO
Description:
It informs the motor power factor.
P009 – Motor Reactive Power
Adjustable
Range:
0.0 to 6553.5 kVAr
Factory
Setting:
-
Proprieties:
RO
Description:
It indicates the average reactive power of the three phases of the motor.
P010 – Motor Active Power
Adjustable
Range:
0.0 to 6553.5 kW
Factory
Setting:
-
Proprieties:
RO
Description:
It indicates the average real power of the three phases of the motor
P011 – Motor Apparent Power
Adjustable
Range:
0.0 to 6553.5 kVA
Factory
Setting:
-
Proprieties:
RO
Description:
It indicates the average apparent power of the three phases of the motor.
P012 – Digital Input I11 to I16 Status
Adjustable
Range:
0 to 63
Factory
Setting:
-
Proprieties:
RO
Description:
It monitors the status of the Control Unit (UC) digital inputs.
Eg: P012 = 12 = 1100b. It means that the digital inputs I13 and I14 are actuated.