Monitoring
6-14 | SRW 01
6
P075 – Alarm Status 1 (binary)
Adjustable
Range:
bit0 = PTC
bit1 = Out of Frequency
bit2 = Undercurrent
bit3 = Overcurrent
Factory
Setting:
-
Proprieties:
RO
Description:
It indicates if any protection actuated indicating only an alarm, without switching off the motor.
E.g.: P075 = 8 = 1000b. It means that the overcurrent protection actuated, but because it was configured for
alarm, the motor has not been stopped.
P076 – Alarm Status 2 (binary)
Adjustable
Range:
bit0 = Phase Loss (Current)
bit1 = Current Imbalance
bit2 = Earth Fault
bit3 = Overload
Factory
Setting:
-
Proprieties:
RO
Description:
It indicates if any protection actuated indicating only an alarm, without switching off the motor.
E.g.: P076 = 8 = 1000b. It means that the overload protection actuated, but because it was configured for
alarm, the motor has not been stopped.
P077 – Alarm Status 3 (binary)
Adjustable
Range:
bit0 = Earth Leakage
bit1 = External Fault
bit2 = No Function
bit3 = No Function
Factory
Setting:
-
Proprieties:
RO
Description:
It indicates if any protection actuated indicating only an alarm, without switching off the motor.
E.g.: P077 = 2 = 0010b. It means that the external fault protection actuated, but because it was configured for
alarm, the motor has not been stopped.
P078 – General Trip Status 2
Adjustable
Range:
0 to 65535
Factory
Setting:
-
Proprieties:
RO
Description:
It indicates if any protection actuated with Trip. It is the unification of the parameters P110 and P111.