Quick Reference of Parameters
0-8 | SRW 01
0
Parameter
Description
Adjustable Range
Factory
Setting
User
Setting
Proprieties Page
P636
Earth Leakage Start up Time Inhibit 1 to 600 s
5 s
Sys, rw
P637
Earth Leakage Short circuit Trip
Inhibit
0 = Disabled
1 = Enabled
0
Sys, rw
P640
Relay Tripping Class
0 = Disabled
1 = Class 5
2 = Class 10
3 = Class 15
4 = Class 20
5 = Class 25
6 = Class 30
7 = Class 35
8 = Class 40
9 = Class 45
2
Sys, rw
P641
Overload Protection Action
0 = Alarm
1 = Switch Off (Trip)
1
Sys, rw
P642
Cooling Time
0 = Disabled
1 to 3600 s =Enabled
0 s
Sys, rw
P643
Auto-reset
0 = Disabled
1 = Enabled
0
Sys, rw
P644
PTC Protection
0 = Disabled
1 = Enabled
0
Sys, rw
P645
PTC Protection Action
0 = Alarm
1 = Switch Off (Trip)
1
Sys, rw
P646
Overload Protection Pre-Alarm
0 to 99 %
80 %
Sys, rw
P647
Overload Pre-alarm Auto-Reset
0 to 99 %
75 %
Sys, rw
P648
Phase Sequence
0 = Disabled
1 = Enabled
0
Sys, rw
P649
Voltage Unbalance
1 to 30 %
5 %
Sys, rw
P650
Voltage Unbalance Time
0 = Disabled
1 to 99 s = Enabled
3 s
Sys, rw
P651
Voltage Unbalance Protection
Action
0 = Alarm
1 = Switch Off (Trip)
1
Sys, rw
P652
Phase Loss Time (Voltage)
0 = Disabled
1 to 99 s = Enabled
3 s
Sys, rw
P653
Phase Loss Protection Action
(Voltage)
0 = Alarm
1 = Switch Off (Trip)
1
Sys, rw
P654
Overvoltage
1 to 30 %
15 %
Sys, rw
P655
Overvoltage Time
0 = Desabilitado
1 to 99 s = Habilitado
3 s
Sys, rw
P656
Overvoltage Protection Action
0 = Alarm
1 = Switch Off (Trip)
1
Sys, rw
P657
Undervoltage
1 to 30 %
15 %
Sys, rw
P658
Undervoltage Time
0 = Disabled
1 to 99 s = Enabled
3 s
Sys, rw
P659
Undervoltage Protection Action
0 = Alarm
1 = Switch Off (Trip)
1
Sys, rw
P660
Underpower
1 to 100 %
30 %
Sys, rw
P661
Underpower Time
0 = Disabled
1 to 99 s = Enabled
0 s
Sys, rw
P662
Underpower Protection Action
0 = Alarm
1 = Switch Off (Trip)
1
Sys, rw
P663
Overpower
1 to 100 %
30 %
Sys, rw
P664
Overpower Time
0 = Disabled
1 to 99 s = Enabled
0 s
Sys, rw
P665
Overpower Protection Action
0 = Alarm
1 = Switch Off (Trip)
1
Sys, rw
P666
Power Under Factor
0.00 to 1.00
0.60
Sys, rw
P667
Power Under Factor Time
0 = Disabled
1 to 99 s = Enabled
0 s
Sys, rw
P668
Power Under Factor Protection
Action
0 = Alarm
1 = Switch Off (Trip)
1
Sys, rw