Parameterization
SRW 01 | 5-57
5
Description:
It defines the power under factor time to shut down the motor or signal an alarm. If P667 = 0, the function is
disabled.
P668 – Power Under Factor Protection Action
Adjustable
Range:
0 = Alarm
1 = Switch Off (Trip)
Factory
Setting:
1
Proprieties:
Sys, rw
Description:
It defines the power under factor protection action.
NOTE!
The power under factor protection is only available when the Current/Voltage Measurement Unit
(UMCT) is used. And it will only be active after the motor start time has elapsed, as per relay trip class
(P640). E.g. Trip class 10, after 10 s.
5.7.24 Power Over Factor
P669 – Power Over Factor
Adjustable
Range:
0.00 to 1.00
Factory
Setting:
0.89
Proprieties:
Sys, rw
Description:
It defines the percentage of power over factor the motor.
P670 – Power Over Factor Time
Adjustable
Range:
0 = Disable
1 to 99 s Enabled
Factory
Setting:
0 s
Proprieties:
Sys, rw
Description:
It defines the overpower time to shut down the motor or signal an alarm. If P670 = 0, the function is disabled.
P671 – Power Over Factor Protection Action
Adjustable
Range:
0 = Alarm
1 = Switch Off (Trip)
Factory
Setting:
1
Proprieties:
Sys, rw
Description:
It defines the power over factor protection action.
NOTE!
The power over factor protection is only available when the Current/Voltage Measurement Unit (UMCT)
is used. And it will only be active after the motor start time has elapsed, as per relay trip class (P640).
E.g. Trip class 10, after 10 s.