Monitoring
SRW 01 | 6-19
6
P116 – Status of Alarm 5 (binary)
Adjustable
Range:
bit0 = Underpower
bit1 = Overpower
bit2 = Power Under Factor
bit3 = Power Over Factor
Factory
Setting:
-
Proprieties:
RO
Description:
It indicates if some protection went off, but without tripping the motor, only alarm.
E.g.: P116 = 8 = 1000b. It means that the power over factor protection went off, but since it is configured as
alarm, the motor is not shut down.