Parameterization
5-20 | SRW 01
5
5.4.6.1 Connection Diagram – Star-Delta Starter
The scheme on
shows an example of the use of the Control Unit (UC) on the Star-
Delta Starting operation mode with drive through digital inputs (P229 or P232 = 0) at 24 Vdc using three wires
(pushbuttons) control logic (P230 = 1) and measurement of delta current.
A2
A1
IC
I16
I15
I14
I13
I12
I11
K1 K2
K3
S1
K1
K2 K3
S0
K1
K2
K3
1
1
1
2
2
2
L1
T1
3
3
3
4
4
4
L2
T2
M
3
~
5
5
5
6
6
6
L3
T3
Q1
Q1
Q2
C1
C3
C4
01
03
04
02
SRW01-UC
R/L1
R/L1
S/L2
T/L3
N
110...240 VAC/VDC 50/60Hz
SRW01-UMC
SRW01-CB
1
2
3
4
5
6
Figure 5.10:
Connection scheme for the Star-Delta Starting operation mode –using digital inputs at 24 Vdc and driven by pushbuttons
(P230=1) and measurement of delta current
ATTENTION!
If the Current Measurement Unit (UMC) is inserted in the delta connection (typical connection), the
motor rated current value (P401) must be adjusted for
1
3
√
of the motor rated current indicated in the
nameplate (In).
Example: Motor rated current (In) = 100 A
P401 = In x
1
3
√
P401 = 100 x
1
3
√
P401 = 57,7 A
The modifications of the scheme for drive through the digital inputs (P229 or P232 = 0) at 24 Vdc, using two wires
(switch) control logic (P230 = 0) is shown on
.
Q1
R/L1
N
A1
IC
I16
I15
I14
I13
I12
I11
K1
K2 K3
S0
110...240 VAC/VDC 50/60 Hz
Figure 5.11:
Detail modification for drive using digital inputs at 24 Vdc and switch drive (P230 = 0)