Installation and Connection
3-4 | SRW 01
3
XC6 terminal strip:
Power supply terminal A2.
Digital outputs – O1, O2, O3 and O4. The outputs O1 and O2 share the common terminal C1.
ATTENTION!
The incorrect application or installation of the SRW 01 may result in damage to its components, faults
or reduction of the useful life of the product due to wiring or application errors, as well as the incorrect
setting of the operation mode, rated current of the motor, incorrect selection of the Current Measuring
Unit (UMC) or Current/Voltage, Measuring Unit (UMCT), incorrect or improper supply source for the
digital inputs, application of voltage on the terminals T1, T2, E1 and E2.
3.3 RELAY POWER SUPPLY
NOTE!
The power supply must be compatible with the SRW 01 nominal voltage.
The SRW 01 is fed through the terminals A1 and A2 from the terminal strips XC1 and XC6, respectively.
Supply voltage:
110 to 240 Vac and Vdc.
24 Vac and Vdc.
NOTE!
Check the nameplate on the product to know which model of the control unit was acquired:
110 to 240 Vac/Vdc or 24 Vac/Vdc supply voltage.
3.4 POWER CABLES
The SRW 01 performs the protection of three-phase and single-phase loads.
The power cable wiring diagram is illustrated in the
(a) Three-phase (b) Single-phase
Figure 3.3:
(a) and (b) Three-phase and single-phase of the Current Measurement Unit (UMC) and Current/Voltage Measurement Unit
(UMCT)