Diagnosis
SRW 01 | 7-3
7
7.3 HISTÓRICO DE DESARMES
The SRW 01 records the last five trips (Trip or error) together with other relevant information to interpret the trip,
such as:
Error code.
Phase current L1.
Phase current L2.
Phase current L3.
Motor thermal protection.
Earth leakage current.
Logical status.
Voltage L1-L2
(*)
.
Voltage L2-L3
(*)
.
Voltage L3-L1
(*)
.
Variable defined by the user in P118.
Variable defined by the user in P119.
(*)
The 0 (zero) value is recorded for the readings of voltage when the Current Measurement Unit (UMC) is used.
P118 – User Defined Parameter 1
Adjustable
Range:
1 to 1109
Factory
Setting:
5
Proprieties:
Sys, rw
Description:
It selects the number of the parameter whose content you wish to register in the eleventh variable of the trip
history. The default value of parameter P118 is 5, thus saving the content of parameter P005 (Line Frequency).
P119 – User Defined Parameter 2
Adjustable
Range:
1 to 1109
Factory
Setting:
20
Proprieties:
Sys, rw
Description:
It selects the number of the parameter whose content you wish to register in the twelfth variable of the trip
history. The default value of parameter P119 is 20, thus saving the content of parameter P020 (Show PTC
Value).