89
1: not save
Once power on, the keypad and terminal frequency
increment will be initialized to 0.
LED tens digit: keep when stop
0: keep when stop
When the VFD stops running, the frequency set value
stays the last modified value.
1: not keep
When the VFD stops running, the set frequency
returns to F0.12.
LED hundreds digit:
UP/DOWN frequency
adjustment
0: invalid
1: valid
When valid, operating with key
, terminal
UP/DOWN can achieve the positive or negative
adjustment of the frequency.
F0.12
Frequency source digital setting 1
0.00Hz~
【
F0.16
】
upper limit
frequency
50.00
When frequency channel is defined as digital given 1
(principle and auxiliary frequency source are both 0),
this function parameter is initial setting frequency
given by keypad digital frequency.
F0.13
Frequency source digital setting 2
0.00Hz~
【
F0.16
】
upper limit
50.00
frequency
When frequency channel is defined as digital given 2
(principle and auxiliary frequency source are both 1),
this function parameter is initial setting frequency
given by VFD terminal.
F0.14
Auxiliary
frequency
source
weight
coefficient K setting
0.01~10.00
1.00
K is the weight coefficient of auxiliary frequency
source, valid when F0.09 is 1~8.
F0.15
Max. Output Freq.
Low freq. stage: MAX
{
50.00,
【
F0.16
】}
~ 300.00
high freq. stage: MAX
{
50.0,
【
F0.16
】}
~ 3000.0
50.00
F0.16
Upper limit freq.
【
F0.17
】
~
【
F0.15
】
50.00
F0.17
Lower limit freq.
0.00Hz~
【
F0.16
】
0.00
The maximum output frequency is highest allowed
frequency for output, and the reference of acc./dec.
time setting, as f
max
showed in the following figure;
basic running frequency is the minimum frequency
when output highest voltage, usually the rated
frequency of motor, as f
b
showed in the following