Acc/Dec time setting at 0 stands for Acc/Dec time 1
(F0.19~F0.20); Acc/Dec time setting at 1, 2, 3 stand for
respectively
Acc/Dec
time
2(F1.13~F1.14),
3(F1.15~F1.16), 4(F1.17~F1.18).
Run time of of these 16 stages are set by run time of
stage X respectively (X: 0~15).
Notice:
1: A stage is ineffective if its run time is set to 0.
2:The control of PLC process including input, pause
and reset can be realized via terminal. See function
definition of F7 terminal.
3: PLC operation direction is determined by
plus/minus of frequency and operation command
together. The running direction of motor can be
changed by external command.
F9.54
Reserved
Reserved
0
F9.55
Traverse control
0~1
0
0: disabled
1: enabled
F9.56
Input method of traverse mode
0~1
0
0: auto
1: terminal config. (manually)
When F9.56 is set at 1, if multi-function terminal
selects function NO.35, the driver will enter traverse
mode. Otherwise, traverse is enabled.
F9.57
Amplitude control
0~1
0
0: fixed amplitude
The reference value of amplitude is max. frequency
F0.15.
1: varied amplitude
The reference value of amplitude is specified channel
frequency.
F9.58
Restart method of traverse mode
0~1
0
0: start to the state before stop
1: just restart, no other requirement
F9.59
Save traverse state upon power failure
0~1
0
0: save
1: not save
The traverse state parameters will be saved when
poweroff. This function is only effective when “start to
the state before stop” mode is selected.