156
press
ENTER
,the password will take into effect
after one minute later.
When there is a need to modify the password, choose
FC.09 function code, press
ENTER
to enter
verification status. After successful authentication,
enter modify status and input the new password,
press
ENTER
, and the password is modified
successfully. One minute later, the new password will
take into effect automatically. For clear password, just
set it at “00000”.
FC.10
Operation limit function
0~1
0
0: disabled
1: enabled
During operation limit, as long as the total operation
time exceeds the time specified by FC.11, the driver
will respond with protection action and coast to stop,
and the keypad displays E-26 (RUNLT). To clear this
fault, just very FC.09 right and set FC.10 at
“0”(disabled).
FC.11
Limit time
0~65535h
0
Note: this parameter can be reset, see description of
FC.09.
FC.12
Freq. decreasing point of transient power
failure
220V:
180V~330V
250V
380V:
300V~550V
450V
Depending
on
model
If the driver bus voltage decrease to lower than FC.12
* rated bus voltage, and the function of immunity to
transient power failure is enabled, the corresponding
action will start.
FC.13
Frequency decreasing factor of transient
power failure
1~100 0: function disabled of
immunity to transient power failure
0
FC.14
Droop control
0.00~10.00Hz
0.00
0.00: droop control function disabled
When multiple drivers are driving the same one load,
the speed difference will cause unbalance distribution
of load, which will result in too much load to the
driver with higher speed. The droop control is to make
speed troop changing with the increase of the load, so
as to equalizing load distribution. This parameter is to
adjust frequency variation of frequency drooping
driver.
When F0.18=1 (high frequency mode), the upper limit