97
F1.32
Delay time of stopping when frequency is
lower than lower limit
0.0~3600.0s
10.0
For details check F1.31 parameter description.
F1.33
zero frequency brake current
0.0~150.0%
0.0
This parameter is the percentage of rated current of
motor.
F1.34
FWD/REV transition time
0.0~100.0s
0.0
The waiting time VFD transit from forward running to
reverse running or the other way around is as t1
showed in the following figure. It is also related to
F1.35 setting.
Fig. F1-7 FWD/REV run dead band time
F1.35
FWD/REV switch mode
0~1
0
0: over zero frequency switch
1: over start frequency switch
F1.36
emergency stop standby deceleration time
0.1~3600.0S
1.0
F1.37
Current continuous time when DC braking
0.0~100.0S
0.0
For details check NO.10 item function description of
discrete input terminal (F7.00~F7.07).
P2 Auxiliary Run Parameter
F2.00
motor type
0~1
0
0: AC asynchronous motor
1: PMSM (permanent magnet synchronous motor)
(reserved)
Asynchronous motor only accepts closed loop
vector control at present.
F2.01
Motor’s rated power
0.4~999.9KW
Depending on
model
F2.02
Motor’s rated frequency
0.01Hz~
【
F0.15
】
max.
output freq.
50.00