102
F4.12
Torque command
0~3
0
This function code is used to set reference input
method of torque control.
0: keypad set
Torque command is given by keypad number. Set
value is introduced in F4.13.
1: AI1
Torque command is set by analog input AI1. The
positive or negative value of AI1 input correspond to
torque command value of forward or reverse
direction.
When using this function, users should set physical
quantity of AI1 input as torque command, and also AI1
setting corresponding curve and AI1 input filtering
time. Refer to function code F6.00~F6.05 for
introduction.
2: AI2
Torque command is set by analog input AI2. The
positive or negative value of AI2 input correspond to
torque command value of forward or reverse
direction.
When using this function, users should set physical
quantity of AI2 input as torque command, and also AI2
setting corresponding curve and AI2 input filtering
time. Refer to function code F6.06~F6.11 for
introduction.
3: RS485 communication
Torque command is given by RS485 communication.
F4.13
Torque set by keypad
-200.0%~200.0%* rated current of
motor
0.0%
This function code corresponds to torque setting value
when torque command is set to given by keypad
number.
F4.14
Speed limit channel 1 of torque control
mode(forward)
0~2
0
This function code is used to set forward speed limit
channel of torque control.
0: keypad number setting 1
See F4.16 setting.
1: AI1
Forward speed limit channel is given by AI1 in
torque control. See function code F6.00~F6.05.
2: AI2
Forward speed limit channel is given by AI2 in
torque control. See function code F6.06~F6.11
description.
F4.15
Speed limit channel selection 2 of torque
control mode(reverse)
0~2
0