9
1.
Check if the voltage of power inlet wire agrees with rated input voltage of VFD.
Injury and fire hazard.
2.
Connect brake resistor or brake unit according to wiring diagram.
Fire hazard.
3.
Choose screw driver and wrench with specified torque to fasten terminals.
Fire hazard.
4.
Do not connect the power input wire to output U, V, W terminals.
It will cause internal damage to VFD if load the voltage on output terminals.
5.
Do not dismantle the front panel cover, only the terminal cover needs to be dismantled when wiring.
It may cause internal damage to VFD.
2.1 Operation Environment
①
No corrosive gases, vapors, dust or oily dust, no direct sunlight.
②
No floating dust and metal particle.
③
Ambient humidity 20%~90% RH.
④
Vibration less than 5.9m/s
2
(0.6g).
⑤
No electromagnetic interference.
⑥
Ambient temperature -10
℃
~40
℃
. Ensure good ventilation when ambient temperature exceeds 40
℃
.
⑦
Use electric cabinet or remote control method in non-standard operation environment and ensure good
ventilation and heat dissipation. The service life of VFD lies in installing environment and operation condition. But
even in standard environment, a long-term continuous running can guarantee a life of no more than 5 years for
electrolytic capacitor and about 3 years for cooling fan. An update or a thorough maintenance in advance is
recommended.