50
F5.18
controller
adjustment cycle
of voltage closed
loop output
0.01~10.00s
0.01s
0.10
×
F5.19
Voltage rising time
0.1~3600.0s
Note: this parameter is only valid for open
loop output mode of complete separated
voltage
0.1s
10.0
o
F5.20
Voltage declining
time
0.1s
10.0
o
F5.21
Voltage feedback
disconnection
treatment
0: alarm and keep running with the
voltage of disconnection moment
1: alarm and keep running with decreased
voltage of amplitude limiting value
2: protection action and free stop
1
0
×
F5.22
Detection value of
voltage feedback
disconnection
0.0~100.0%*rated voltage of motor
0.1%
2.0%
o
F5.23
Detection time of
voltage feedback
disconnection
0.0~100.0s
0.1s
10.0
o
F5.24
Limit voltage of
voltage feedback
disconnection
0.0~100.0%*rated voltage of motor
Note: this voltage represents the output
voltage of VFD, and reasonable setting of
this parameter could prevent machine
damage resulting from voltage overshoot
at disconnection moment.
0.1%
80.0%
o
F6 Group - Analog Quantity and Pulse Input and Output Parameters
F6.00
AI1 input
corresponding
0: speed command (output
freq.,-100.0%~100.0%)
1
0
×