4.2 Detailed Function Description
F0 system management parameter
F0.00
User password
0~65535
0
User password setting function could prevent
unauthorized person from checking and modifying the
function parameters.
To avoid misoperation, user password less than 10 is
invalid.
When setting the user password, input a number not
less than 10, press
E N T E R
to confirm, and the
password will take into effect after one minute.
To modify the password, choose F0.00 function code,
and
press
E N T E R
to
enter
password
authentification status. After the authentification is
successfully done, enter modifying status and input a
new password, press
E N T E R
to confirm, and the
modifying will be done successfully. New password
will take into effect after 3 minutes.
Note:
Please keep the password carefully, and seek help
from the manufacture once lost the password.
F0.01
Control
software
version
1.00~99.99
1.01
F0.02
Keypad
software
version
1.00~99.99
1.00
F0.03
VFD rated power
0.4~999.9KW(G/P)
Depending on
model
The above function codes are used for indicating the
relevant information of VFD, which can not be
modified but only checked
F0.04
VFD type
0~1
0
0: G type (constant torque load type)
1: P type (fan and water pump load type)
For our VFD products, G/P type are combined, i.e. G
type inverter can be used as P type inverter with
power of one grade higher, but only if the function
code is set with corresponding value.
F0.05
Control mode
0~4
Depending on model
0: common V/F control
This control mode is used when there is a need to
drive one more motors with a single inverter and
there is no access to the parameters of controlled
motor. This control mode is most commonly used and
applied in any circumstance where no strict
requirement is needed for the motor control
performance.