177
Example:
Name
Frame format
Read parameter value of
F0.12
Send frame: 01H 13H 000CH 0001H 85CAH
Return frame: 01H 13H 02H 1388H B1D2H
Read parameter value +
attribute value of F0.12
Send frame: 01H 13H 000CH 0002H C5CBH
Return frame: 01H 13H 04H 1388H 0322H FCE4H
Read parameter value +
attribute value + min.value
of F0.12
Send frame: 01H 13H 000CH 0003H 040BH
Return frame: 01H 13H 06H 1388H 0322H 0000H 628BH
Read parameter value +
min.value + max.value of
F0.12
Send frame: 01H 13H 000CH 0004H 45CBH
Return frame: 01H 13H 08H 1388H 0322H 0000H 1388H 2831H
5.3 Functions of other Register Address:
Function
Address
Description
VFD operation
status
A000H(1A00H)
Byte
Bit
Meaning
Byte1
Bit7
0: no action
1: overload pre-alarm