03TA Service Manual
TROUBLESHOOTING
2/14/07
8-5
SYMPTOM: Freeze-up due to ice failing to discharge.
POSSIBLE CAUSE
POSSIBLE REMEDY
Insufficient heat for thawing because of low
condensing pressure, non-condensables
(usually air) in system, low refrigerant charge,
or thaw gas solenoid valve stuck closed.
The head pressure should be maintained at
approximately 210 PSIG for R-22 or 250
PSIG for R-404a, which relates to 105
o
F
(37.8 C). This is done by a water-regulating
valve (water-cooled units) FIGURE 9-5A,
Section 9, or a Fan cycling switch (air-cooled
units) FIGURE 9-5B, Section 9. If non-
condensables are present with the refrigerant,
the saturated temperature will not relate to the
pressure reading at the receiver. The
refrigerant level in the receiver should be near
the operating mark at the end of a freezing
cycle to provide enough volume for
harvesting. (1" = approx. 5.5 lbs. of R-22 or
R-404a).
Thawing time too short.
Check the thaw timer (T), which should be
adjusted to allow all the ice to clear the cutter
and ice discharge opening with at least 30
seconds to spare.
Cutter or cutter disc does not turn.
Check cutter reducer and drive gear for proper
operation and alignment. Check for broken
cutter disc or drive pin and replace as
necessary.
Ice backs up into cutter or discharge opening,
jamming cutter
Ice mushy due to concentration of solids in the
water tank. Perform "Cleaning Procedure" and
check automatic and adjustable blowdown. If
the machine discharges ice into a chute, it
should slope at an angle of 30 degrees for
cylinder ice and 45 degrees for crushed ice.
Check bin stat or level control to make sure it
will stop the machine before ice backs-up into
the cutter.
Extended freeze period.
Check
freezer pressure switch adjustment; see
FIGURE 9-3, Section 9, (Freezer Pressure
Switch) and TABLE 11-6, Section 11
(Operating Vitals).
Compressor not unloading.
Check compressor amps during harvest. A
noticeable drop in amperage should occur.
Check unloader solenoid coil. If coil is okay,
replace unloader head assembly.
Содержание TUBE-ICE 03TA
Страница 10: ...5 24 11 Blank page ...
Страница 14: ...03TA Service Manual INTRODUCTION 4 21 14 1 4 FIGURE 1 1 Assembly Air Cooled Front View ...
Страница 15: ...03TA Service Manual INTRODUCTION 4 21 14 1 5 FIGURE 1 2 Assembly Air Cooled Rear View ...
Страница 16: ...03TA Service Manual INTRODUCTION 4 21 14 1 6 FIGURE 1 3 Assembly Air Cooled Right Side View ...
Страница 17: ...03TA Service Manual INTRODUCTION 4 21 14 1 7 FIGURE 1 4 Assembly Water Cooled Front View ...
Страница 18: ...03TA Service Manual INTRODUCTION 4 21 14 1 8 FIGURE 1 5 Assembly Water Cooled Rear View ...
Страница 19: ...03TA Service Manual INTRODUCTION 4 21 14 1 9 FIGURE 1 6 Assembly Water Cooled Right Side View ...
Страница 20: ...03TA Service Manual INTRODUCTION 4 21 14 1 10 BLANK ...
Страница 44: ...5 24 11 Blank page ...
Страница 47: ...03TA Service Manual HOW YOUR TUBE ICE MACHINE WORKS 4 11 2014 4 3 FIGURE 4 1 Water Cooled Piping Schematic ...
Страница 48: ...03TA Service Manual HOW YOUR TUBE ICE MACHINE WORKS 3 31 2014 4 4 FIGURE 4 2 Air Cooled Piping Schematic ...
Страница 54: ...5 24 11 Blank page ...
Страница 56: ...03TA Service Manual ELECTRICAL CONTROLS 4 17 14 6 2 FIGURE 6 2 Control Panel Components Standard ...
Страница 61: ...03TA Service Manual ELECTRICAL CONTROLS 3 31 14 6 7 FIGURE 6 3 Electrical Schematic All Voltages 50 60 Hz ...
Страница 102: ...03TA Service Manual SERVICE OPERATIONS 4 2 14 9 20 FIGURE 9 14 Cutter Water Tank and Drive Gear Assembly ...
Страница 104: ...5 24 11 Blank page ...
Страница 111: ...03TA Service Manual 10 7 OPTIONS AND ACCESSORIES FIGURE 10 4 Wiring Schematic Mid Size Machine P112 P118 P18XT ...
Страница 112: ...5 24 11 Blank page ...
Страница 122: ...03TA Service Manual INDEX 4 21 14 12 4 ...