Coding
Code 2
(cont.)
Coding in the delivered condition
Possible change
General
7F
:
1
Detached house
7F
:
0
Apartment block
Separate settings for
holiday and time programs
are possible for DHW
heating (see page 53) for
every heating circuit
80
:
1
A fault message is
80
:
0
Immediate fault message
g
displayed, providing a fault
is active for at least 5s
80
:
2
to
80
:
199
The minimum fault
duration, until a message is
displayed, is adjustable
from 10 to 995s;
1 setting step
¢
5s
81
:
1
Automatic summer/winter
time changeover
Note
81
:
0
Manual summer/winter
changeover
Note
coding addresses 82 to 87
only possible if code 81: 1
has been selected
81
:
2
The use of the radio clock
receiver will be recognised
automatically
82
:
3
Summer starts: March
82
:
1
to
82
:12
January
to
December
83
:
5
Summer starts:
last week of month
83
:
1
to
83
:5
Week 1
to
Week 5
84
:
7
Summer starts:
last day of the week
(Sunday)
84
:
1
to
84
:7
Monday
to
Sunday
85
:
10
Winter starts:
October
85
:
1
to
85
:12
January
to
December
5862700GB
Содержание Vitotronic 200 KW2
Страница 22: ...22 Installation Installing the top part of the control unit 5862 700 GB 7 5 1 4 6 2 3 ...
Страница 23: ...23 Installation Opening the control unit 5862 700 GB 3 2 1 ...
Страница 104: ...104 Coding 5862 700 GB ...
Страница 106: ...106 Parts list Parts list cont 5862 700 GB 070 010 042 043 065 019 020 018 074 013 015 074 040 041 ...
Страница 108: ...108 Connection and wiring diagram Connection and wiring diagram 5862 700 GB F2 4A slow 250V F1 slow 6 3A 250V ...
Страница 118: ...118 5862 700 GB ...
Страница 119: ...119 5862 700 GB ...